Application examples
205
10
Example setting of parameters
The following shows mechanical specifications and parameter settings required for configuring the system shown as the
application example. The parameter settings are examples for a 7.5 kW motor and the 11 kW inverter used for the winding
roller.
Item
Specification
Item
Specification
Minimum roll diameter
280 mm
Line speed command
Analog signal, 0 to 10 V input (90
seconds cushion time enabled at
acceleration/deceleration)
Maximum roll diameter
400 mm
Gear ratio
1/1.2
Initial roll diameter
calculation
Disabled
Maximum speed of the
actual line
2000 m/min
Roll diameter storage
Enabled
Dancer signal
0 to 10 V input
Tension setting output
Required
Pr.
Parameter name
Initial
value
Setting
value
Remarks
7
Acceleration time
15 s
0.1 s
Use these parameters to improve trackability of the dancer
feedback speed control.
(In this example, 0.1 seconds is applied to avoid the influence
of external noises. Setting a larger value worsen the
trackability.)
8
Deceleration time
15 s
0.1 s
9
Electronic thermal O/L relay
Inverter
rated
current
0 A
Setting for a specific motor for Vector control (motor with built-
in thermal protector).
10
DC injection brake operation
frequency
3 Hz
0 Hz
52
Operation panel main monitor
selection
0
22
Set "22" (Roll diameter) for monitoring.
Or use any of
Pr.774 to Pr.776
when using the 3-line monitor
screen on the PU.
Other monitor items related to this application and their
setting values are as follows:
26 (Line speed command), 27 (Actual line speed), 28 (Dancer
compensation speed), 29 (Winding length), 52 (PID set
point), 53 (PID measured value), and 54 (PID deviation).
71
Applied motor
0
30
30: Setting for the Mitsubishi Electric Vector control dedicated
motor SF-V5RU.
73
Analog input selection
1
10
10: Terminal 2 input between 0 to 10 V for the line speed and
terminal 1 input between 0 to 10 V for the dancer signal with
reversible polarity.
79
Operation mode selection
0
2
2: External operation mode only.
80
Motor capacity
9999
7.5 kW
Set these parameters according to the motor.
81
Number of motor poles
9999
4 (poles)
83
Rated motor voltage
200 V
164 V
84
Rated motor frequency
9999
51 Hz
128
PID action selection
0
41
41: Dancer control enabled (forward action)
(Compensation direction of the dancer signal is reversed
since the lower limit of the dancer signal output is 8 V and the
upper limit is 2 V.)
129
PID proportional band
100%
250%
Performing tension PI gain tuning allows setting these
parameters.
130
PID integral time
1 s
5 s
133
PID action set point
500%
550%
Set
Pr.52
= "86" (Terminal 1 input after calibration in %) to
check the upper and lower limit of the dancer roll position. Set
the target position (neutral position) in this parameter
according to the check result.
134
PID differential time
9999
0.05 s
To improve trackability of a mechanical extraneous
disturbance (variation), set 0.01 seconds at first, and change
the setting to a slightly larger value as required. (Set the
minimum possible value because setting a too large value
causes hunting.)
180
RL terminal function selection
0
114
114: Tension control selection (X114) signal ON (Setting "114"
is required for tension control.)
181
RM terminal function selection
1
109
109: Stored winding diameter clear (X109) signal ON (Setting
"109" clears the stored roll diameter.)
Содержание A800 Plus Series
Страница 240: ...239 MEMO ...