Parameter list (by parameter number)
13
2
118
N021
PU communication speed
48, 96, 192, 384, 576,
768, 1152
1
192
─
119
─
PU communication stop bit
length / data length
0, 1, 10, 11
1
1
─
N022
PU communication data length
0, 1
0
N023
PU communication stop bit
length
0, 1
1
120
N024
PU communication parity check
0 to 2
1
2
─
121
N025
Number of PU communication
retries
0 to 10, 9999
1
1
─
122
N026
PU communication check time
interval
0, 0.1 to 999.8 s, 9999
0.1 s
9999
─
123
N027
PU communication waiting time
setting
0 to 150 ms, 9999
1 ms
9999
─
124
N028
PU communication CR/LF
selection
0 to 2
1
1
─
125
T022
Terminal 2 frequency setting
gain frequency
0 to 590 Hz
0.01 Hz
60 Hz
50 Hz
─
126
T042
Terminal 4 frequency setting
gain frequency
0 to 590 Hz
0.01 Hz
60 Hz
50 Hz
─
127
A612
PID control automatic
switchover frequency
0 to 590 Hz, 9999
0.01 Hz
9999
─
128
A610
PID action selection
0, 40, 41
1
0
R100
129
A613
PID proportional band
0.1 to 1000%, 9999
0.1%
100%
R110
130
A614
PID integral time
0.1 to 3600 s, 9999
0.1 s
1 s
R111
131
A601
PID upper limit
400 to 600%, 9999
0.1%
9999
,
132
A602
PID lower limit
400 to 600%, 9999
0.1%
9999
,
133
A611
PID action set point
400 to 600%
0.01%
500%
R101
134
A615
PID differential time
0.01 to 10 s, 9999
0.01 s
9999
R112
135
R161
Integral clamp (positive polarity)
0 to 100%, 9999
0.1%
9999
136
R162
Integral clamp (negative
polarity)
0 to 100%, 9999
0.1%
9999
137
R163
PID upper/lower limit hysteresis
width
0 to 100%, 9999
0.1%
9999
,
140
F200
Backlash acceleration stopping
frequency
0 to 590 Hz
0.01 Hz
1 Hz
─
141
F201
Backlash acceleration stopping
time
0 to 360 s
0.1 s
0.5 s
─
142
F202
Backlash deceleration stopping
frequency
0 to 590 Hz
0.01 Hz
1 Hz
─
143
F203
Backlash deceleration stopping
time
0 to 360 s
0.1 s
0.5 s
─
144
M002
Speed setting switchover
0, 2, 4, 6, 8, 10, 12, 102,
104, 106, 108, 110, 112
1
4
─
145
E103
PU display language selection
0 to 7
1
─
─
147
F022
Acceleration/deceleration time
switching frequency
0 to 590 Hz, 9999
0.01 Hz
9999
─
148
H620
Stall prevention level at 0 V
input
0 to 400%
0.1%
150%
─
149
H621
Stall prevention level at 10 V
input
0 to 400%
0.1%
200%
─
150
M460
Output current detection level
0 to 400%
0.1%
150%
─
151
M461
Output current detection signal
delay time
0 to 10 s
0.1 s
0 s
─
152
M462
Zero current detection level
0 to 400%
0.1%
5%
─
Pr.
Pr.
group
Name
Setting range
Minimum
setting
increments
Initial value Refer
to
page
Customer
setting
FM
CA
Simple
Simple
Simple
Simple
Simple
Simple