Parameter list (by parameter number)
10
2
PARAMETER LIST
2.1
Parameter list (by parameter number)
For simple variable-speed operation of the inverter, the initial values of the parameters may be used as they are. Set the
necessary parameters to meet the load and operational specifications. Parameter's setting, change and check can be made
on the operation panel (FR-DU08).
NOTE
•
indicates simple mode parameters. Use
Pr.160 User group read selection
to indicate the simple mode parameters
only (initial setting is to indicate the extended mode parameters).
• The changing of the parameter settings may be restricted in some operating statuses. Use
Pr.77 Parameter write selection
to change the setting of the restriction.
• Refer to
for instruction codes for communication and availability of Parameter clear, all clear, and Parameter copy.
Pr.
Pr.
group
Name
Setting range
Minimum
setting
increments
Initial value Refer
to
page
Customer
setting
FM
CA
0 G000
Torque boost
0 to 30%
0.1%
6%
4%
3%
2%
1%
1 H400
Maximum frequency
0 to 120 Hz
0.01 Hz
60 Hz
2 H401
Minimum frequency
0 to 120 Hz
0.01 Hz
0 Hz
3 G001
Base frequency
0 to 590 Hz
0.01 Hz
60 Hz
50 Hz
4 D301
Multi-speed setting (high
speed)
0 to 590 Hz
0.01 Hz
60 Hz
50 Hz
5 D302
Multi-speed setting (middle
speed)
0 to 590 Hz
0.01 Hz
30 Hz
6 D303
Multi-speed setting (low
speed)
0 to 590 Hz
0.01 Hz
10 Hz
7 F010
Acceleration time
0 to 3600 s
0.1 s
8 F011
Deceleration time
0 to 3600 s
0.1 s
9 H000
Electronic thermal O/L
relay
0.01 A
Inverter rated
current
0.1 A
10
G100
DC injection brake operation
frequency
0 to 120 Hz, 9999
0.01 Hz
3 Hz
11
G101
DC injection brake operation
time
0 to 10 s, 8888
0.1 s
0.5 s
12
G110
DC injection brake operation
voltage
0 to 30%
0.1%
4%
2%
1%
13
F102
Starting frequency
0 to 60 Hz
0.01 Hz
0.5 Hz
14
G003
Load pattern selection
0 to 5, 12 to 15
1
0
15
D200
Jog frequency
0 to 590 Hz
0.01 Hz
5 Hz
16
F002
Jog acceleration/deceleration
time
0 to 3600 s
0.1 s
0.5 s
17
T720
MRS input selection
0, 2, 4
1
0
18
H402
High speed maximum frequency
0 to 590 Hz
0.01 Hz
60 Hz
19
G002
Base frequency voltage
0 to 1000 V, 8888, 9999
0.1 V
9999
8888
20
F000
Acceleration/deceleration
reference frequency
1 to 590 Hz
0.01 Hz
60 Hz
50 Hz
21
F001
Acceleration/deceleration time
increments
0, 1
1
0
22
H500
Stall prevention operation level
(Torque limit level)
0 to 400%
0.1%
150%
Simple
Simple
Simple
Simple
Simple
Simple
Simple
Simple
Simple
Simple
Simple
Simple
Simple
Simple
Simple
Simple
Simple
Simple
Simple
Simple
Simple
Simple
Simple
Simple
Simple
Simple
Simple
Simple
Simple
Simple
Simple
Simple
Simple