PID control during emergency drive operation
• During emergency drive operation in the PID control mode, the operation is performed under PID control using
the
Pr.524
setting as a set point. Input the measured values in the method set in
Pr.128
or
Pr.753
.
• When the PID control mode is selected for emergency drive, the PID action during emergency drive operation is
as follows depending on the PID control setting.
• While the "retry" (
Pr.523
= "22[], 32[]") is selected in the PID control mode, if a retry occurs at an occurrence of
E.CPU, E.1 to E.3, or E.5 to E.7 during emergency drive operation, the operation is performed not under PID
control but with the fixed frequency.
Use
Pr.1013 Emergency drive running speed after retry reset
to set the fixed frequency.
Operation of protective functions during emergency drive
• Operation of protective functions during emergency drive is as follows.
*1
While the switchover to the commercial power supply operation during emergency drive operation is enabled, when the same
protective function is activated twice consecutively, the retry is attempted up to twice.
*2
In normal operation (
Pr.523
= "200 or 300"), the start signal is turned OFF at the same time the retry function resets the protective
function. Input the start signal again to resume the operation.
Item
PID control action
Set point / measured
value input setting
Deviation input setting
Without PID control
setting
Measured value input selection (
Pr.128
,
Pr.753
) Held
Terminal 4 input
Terminal 4 input
Forward action / reverse action selection
(
Pr.128
,
Pr.753
)
Held
Held
Reverse action
Proportional band (
Pr.129
,
Pr.756
)
Held
Held
100% (initial value)
Integral time (
Pr.130
,
Pr.757
)
Held
Held
1 s (initial setting)
Differential time (
Pr.134
,
Pr.758
)
Held
Held
Not used (initial setting)
Applied to the frequency / calculation only
(
Pr.128
,
Pr.753
)
Applied to the frequency Applied to the frequency Applied to the frequency
Dancer control
Invalid
Invalid
Invalid
Other PID-related settings
Held
Held
Held
Protective
function
Operation during
emergency drive
Protective
function
Operation during
emergency drive
Protective
function
Operation during
emergency drive
E.OC1
Retry
E.OP3
The function is disabled.
E.ECA
The function is disabled.
E.OC2
Retry
E.16
The function is disabled.
E.MB1
The function is disabled.
E.OC3
Retry
E.17
The function is disabled.
E.MB2
The function is disabled.
E.OV1
Retry
E.18
The function is disabled.
E.MB3
The function is disabled.
E.OV2
Retry
E.19
The function is disabled.
E.MB4
The function is disabled.
E.OV3
Retry
E.20
The function is disabled.
E.MB5
The function is disabled.
E.THT
Retry
E.PE
Output shutoff
E.MB6
The function is disabled.
E.THM
Retry
E.PUE
The function is disabled.
E.MB7
The function is disabled.
E.FIN
Retry
E.RET
Output shutoff
E.EP
The function is disabled.
E.IPF
The function is disabled.
E.PE2
Output shutoff
E.MP
The function is disabled.
E.UVT
The function is disabled.
E.CPU
Retry
E.EF
The function is disabled.
E.ILF
The function is disabled.
E.CTE
The function is disabled.
E.IAH
The function is disabled.
E.OLT
Retry
E.P24
The function is disabled.
E.LCI
The function is disabled.
E.SOT
Retry
E.CDO
Retry
E.PCH
The function is disabled.
E.LUP
The function is disabled.
E.IOH
Output shutoff
E.PID
The function is disabled.
E.LDN
The function is disabled.
E.SER
The function is disabled.
E.1
Retry
*2
E.BE
Retry
*1
E.AIE
The function is disabled.
E.2
Retry
*2
E.GF
Retry
E.USB
The function is disabled.
E.3
Retry
*2
E.LF
The function is disabled.
E.SAF
Retry
*1
E.5
Retry
*2
E.OHT
Retry
E.PBT
Retry
*1
E.6
Retry
*1*2
E.PTC
Retry
E.OS
The function is disabled.
E.7
Retry
*1*2
E.OPT
The function is disabled.
E.OSD
The function is disabled.
E.11
The function is disabled.
E.OP1
The function is disabled.
E.ECT
The function is disabled.
E.13
Output shutoff
E.OP2
The function is disabled.
E.OD
The function is disabled.