PARAMETER LIST
17
791
Acceleration time in
low-speed range
0 to 3600s, 9999 9999
792
Deceleration time in
low-speed range
0 to 3600s, 9999 9999
799
Pulse increment setting
for output power
0.1, 1, 10,
100, 1000kWh
1kWh
800
Control method
selection
0 to 6, 9 to 14,
20, 100 to 106,
109 to 114
20
801
Output limit level
0 to 400%, 9999 9999
802
Pre-excitation selection 0, 1
0
803
Constant output range
torque characteristic
selection
0 to 2, 10, 11
0
804
Torque command
source selection
0 to 6
0
805
Torque command value
(RAM)
600 to 1400%
1000%
806
Torque command value
(RAM, EEPROM)
600 to 1400%
1000%
807
Speed limit selection
0 to 2
0
808
Forward rotation speed
limit/speed limit
0 to 400Hz
60/50Hz
809
Reverse rotation speed
limit/reverse-side speed
limit
0 to 400Hz, 9999
9999
810
Torque limit input
method selection
0 to 2
0
811
Set resolution
switchover
0, 1, 10, 11
0
812
Torque limit level
(regeneration)
0 to 400%, 9999
9999
813
Torque limit level (3rd
quadrant)
0 to 400%, 9999
9999
814
Torque limit level (4th
quadrant)
9999
815
Torque limit level 2
9999
816
Torque limit level during
acceleration
9999
817
Torque limit level during
deceleration
9999
818
Easy gain tuning
response level setting
1 to 15
2
819
Easy gain tuning
selection
0 to 2
0
820
Speed control P gain 1 0 to 1000%
60%
821
Speed control integral
time 1
0 to 20s
0.333s
822
Speed setting filter 1
0 to 5s, 9999
9999
823
Speed detection filter 1 0 to 0.1s
0.001s
824
Torque control P gain 1
(current loop
proportional gain)
0 to 500%
100%
825
Torque control integral
time 1 (current loop
integral time)
0 to 500ms
5ms
826
Torque setting filter 1
0 to 5s, 9999
9999
827
Torque detection filter 1 0 to 0.1s
0s
828
Model speed control
gain
0 to 1000%
60%
829
Number of machine end
encoder pulses
0 to 4096, 9999 9999
830
Speed control P gain 2 0 to 1000%, 9999 9999
831
Speed control integral
time 2
0 to 20s, 9999
9999
832
Speed setting filter 2
0 to 5s, 9999
9999
833
Speed detection filter 2 0 to 0.1s, 9999 9999
834
Torque control P gain 2 0 to 500%, 9999
9999
835
Torque control integral
time 2
0 to 500ms, 9999 9999
836
Torque setting filter 2
0 to 5s, 9999
9999
837
Torque detection filter 2 0 to 0.1s, 9999 9999
840
Torque bias selection
0 to 3, 24, 25,
9999
9999
841
Torque bias 1
600 to 1400%,
9999
9999
842
Torque bias 2
600 to 1400%,
9999
9999
843
Torque bias 3
600 to 1400%,
9999
9999
844
Torque bias filter
0 to 5s, 9999
9999
845
Torque bias operation
time
0 to 5s, 9999
9999
846
Torque bias balance
compensation
0 to 10V, 9999
9999
847
Fall-time torque bias
terminal 1 bias
0 to 400%, 9999
9999
848
Fall-time torque bias
terminal 1 gain
0 to 400%, 9999
9999
849
Analog input offset
adjustment
0 to 200%
100%
850
Brake operation
selection
0 to 2
0
851
Control terminal option-
Number of encoder
pulses
0 to 4096
2048
Pr.
Name
Setting
range
Initial
value
852
Control terminal option-
Encoder rotation
direction
0, 1, 100, 101
1
853
Speed deviation time
0 to 100s
1s
854
Excitation ratio
0 to 100%
100%
855
Control terminal option-
Signal loss detection
enable/disable
selection
0, 1
0
858
Terminal 4 function
assignment
0, 1, 4, 9999
0
859
Torque current/Rated
PM motor current
0 to 500A,
9999
9999
0 to 3600A,
9999
860
Second motor torque
current/Rated PM
motor current
0 to 500A,
9999
9999
0 to 3600A,
9999
862
Encoder option
selection
0, 1
0
863
Control terminal option-
Encoder pulse division
ratio
1 to 32767
1
864
Torque detection
0 to 400%
150%
865
Low speed detection
0 to 590Hz
1.5Hz
866
Torque monitoring
reference
0 to 400%
150%
867
AM output filter
0 to 5s
0.01s
868
Terminal 1 function
assignment
0 to 6, 9999
0
869
Current output filter
0 to 5s
0.02s
870
Speed detection
hysteresis
0 to 5Hz
0Hz
872
Input phase loss
protection selection
0, 1
0
873
Speed limit
0 to 400Hz
20Hz
874
OLT level setting
0 to 400%
150%
875
Fault definition
0, 1
0
876
Thermal protector input 0, 1
1
877
Speed feed forward
control/model adaptive
speed control selection
0 to 2
0
878
Speed feed forward
filter
0 to 1s
0s
879
Speed feed forward
torque limit
0 to 400%
150%
880
Load inertia ratio
0 to 200 times
7 times
881
Speed feed forward
gain
0 to 1000%
0%
882
Regeneration
avoidance operation
selection
0 to 2
0
883
Regeneration
avoidance operation
level
300 to 1200V
DC380/
DC760V
884
Regeneration
avoidance at
deceleration detection
sensitivity
0 to 5
0
885
Regeneration avoidance
compensation frequency
limit value
0 to 590Hz, 9999 6Hz
886
Regeneration
avoidance voltage gain 0 to 200%
100%
888
Free parameter 1
0 to 9999
9999
889
Free parameter 2
0 to 9999
9999
891
Cumulative power
monitor digit shifted
times
0 to 4, 9999
9999
892
Load factor
30 to 150%
100%
893
Energy saving monitor
reference (motor
capacity)
0.1 to 55kW
Inverter
rated
capacity
0 to 3600kW
894
Control selection during
commercial power-
supply operation
0 to 3
0
895
Power saving rate
reference value
0, 1, 9999
9999
896
Power unit cost
0 to 500, 9999
9999
897
Power saving monitor
average time
0, 1 to 1000h,
9999
9999
898
Power saving
cumulative monitor
clear
0, 1, 10, 9999
9999
899
Operation time rate
(estimated value)
0 to 100%, 9999 9999
C0
(900)
FM/CA terminal
calibration
―
―
C1
(901)
AM terminal calibration
―
―
C2
(902)
Terminal 2 frequency
setting bias frequency
0 to 590Hz
0Hz
C3
(902)
Terminal 2 frequency
setting bias
0 to 300%
0%
125
(903)
Terminal 2 frequency
setting gain frequency
0 to 590Hz
60/50Hz
Pr.
Name
Setting
range
Initial
value
C4
(903)
Terminal 2 frequency
setting gain
0 to 300%
100%
C5
(904)
Terminal 4 frequency
setting bias frequency
0 to 590Hz
0Hz
C6
(904)
Terminal 4 frequency
setting bias
0 to 300%
20%
126
(905)
Terminal 4 frequency
setting gain frequency
0 to 590Hz
60/50Hz
C7
(905)
Terminal 4 frequency
setting gain
0 to 300%
100%
C12
(917)
Terminal 1 bias
frequency (speed)
0 to 590Hz
0Hz
C13
(917)
Terminal 1 bias (speed) 0 to 300%
0%
C14
(918)
Terminal 1 gain
frequency (speed)
0 to 590Hz
60/50Hz
C15
(918)
Terminal 1 gain (speed) 0 to 300%
100%
C16
(919)
Terminal 1 bias
command (torque/
magnetic flux)
0 to 400%
0%
C17
(919)
Terminal 1 bias (torque/
magnetic flux)
0 to 300%
0%
C18
(920)
Terminal 1 gain
command (torque/
magnetic flux)
0 to 400%
150%
C19
(920)
Terminal 1 gain (torque/
magnetic flux)
0 to 300%
100%
C8
(930)
Current output bias
signal
0 to 100%
0%
C9
(930)
Current output bias
current
0 to 100%
0%
C10
(931)
Current output gain
signal
0 to 100%
100%
C11
(931)
Current output gain
current
0 to 100%
100%
C38
(932)
Terminal 4 bias
command (torque/
magnetic flux)
0 to 400%
0%
C39
(932)
Terminal 4 bias (torque/
magnetic flux)
0 to 300%
20%
C40
(933)
Terminal 4 gain
command (torque/
magnetic flux)
0 to 400%
150%
C41
(933)
Terminal 4 gain (torque/
magnetic flux)
0 to 300%
100%
C42
(934)
PID display bias
coefficient
0 to 500.00,
9999
9999
C43
(934)
PID display bias analog
value
0 to 300%
20%
C44
(935)
PID display gain
coefficient
0 to 500.00,
9999
9999
C45
(935)
PID display gain analog
value
0 to 300%
100%
977
Input voltage mode
selection
0, 1
0
989
Parameter copy alarm
release
100
990
PU buzzer control
0, 1
1
991
PU contrast adjustment 0 to 63
58
992
Operation panel setting
dial push monitor
selection
0 to 3, 5 to 14,
17 to 20,
22 to 36,
38 to 46,
50 to 57, 61, 62,
64, 67, 71 to 75,
87 to 98, 100
0
994
Droop break point gain 0.1 to 100%, 9999 9999
995
Droop break point
torque
0.1 to 100%
100%
997
Fault initiation
0 to 255, 9999
9999
998
PM parameter
initialization
0, 3003, 3103,
8009, 8109,
9009, 9109
0
999
Automatic parameter
setting
1, 2,10 to 13,
20, 21, 9999
9999
1000 Direct setting selection 0 to 2
0
1002 Lq tuning target current
adjustment coefficient
50 to 150%,
9999
9999
1003 Notch filter frequency
0, 8 to 1250Hz
0
1004 Notch filter depth
0 to 3
0
1005 Notch filter width
0 to 3
0
1006 Clock (year)
2000 to 2099
2000
1007 Clock (month, day)
101 to 131,
201 to 229,
301 to 331,
401 to 430,
501 to 531,
601 to 630,
701 to 731,
801 to 831,
901 to 930,
1001 to 1031,
1101 to 1130,
1201 to 1231
101
Pr.
Name
Setting
range
Initial
value