PARAMETER LIST
129
PID proportional band
0.1 to 1000%,
9999
100%
130
PID integral time
0.1 to 3600s,
9999
1s
131
PID upper limit
0 to 100%, 9999 9999
132
PID lower limit
0 to 100%, 9999 9999
133
PID action set point
0 to 100%, 9999 9999
134
PID differential time
0.01 to 10s,
9999
9999
135
Electronic bypass
sequence selection
0, 1
0
136
MC switchover interlock
time
0 to 100s
1s
137
Start waiting time
0 to 100s
0.5s
138
Bypass selection at a
fault
0, 1
0
139
Automatic switchover
frequency from inverter
to bypass operation
0 to 60Hz, 8888,
9999
9999
140
Backlash acceleration
stopping frequency
0 to 590Hz
1Hz
141
Backlash acceleration
stopping time
0 to 360s
0.5s
142
Backlash deceleration
stopping frequency
0 to 590Hz
1Hz
143
Backlash deceleration
stopping time
0 to 360s
0.5s
144
Speed setting
switchover
0, 2, 4, 6, 8, 10,
12, 102, 104,
106, 108, 110,
112
4
145
PU display language
selection
0 to 7
―
147
Acceleration/
deceleration time
switching frequency
0 to 590Hz, 9999
9999
148
Stall prevention level at
0 V input
0 to 400%
150%
149
Stall prevention level at
10 V input
0 to 400%
200%
150
Output current
detection level
0 to 400%
150%
151
Output current
detection signal delay
time
0 to 10s
0s
152
Zero current detection
level
0 to 400%
5%
153
Zero current detection
time
0 to 10s
0.5s
154
Voltage reduction
selection during stall
prevention operation
0, 1, 10, 11
1
155
RT signal function
validity condition
selection
0, 10
0
156
Stall prevention
operation selection
0 to 31, 100, 101 0
157
OL signal output timer
0 to 25s, 9999
0s
158
AM terminal function
selection
1 to 3, 5 to 14,
17, 18, 21, 24,
32 to 34, 36, 46,
50, 52 to 54, 61,
62, 67, 70,
87 to 98
1
159
Automatic switchover
frequency range from
bypass to inverter
operation
0 to 10Hz, 9999 9999
User group read
selection
0, 1, 9999
0
161
Frequency setting/key
lock operation selection 0, 1, 10, 11
0
162
Automatic restart after
instantaneous power
failure selection
0 to 3, 10 to 13,
1000 to 1003,
1010 to 1013
0
163
First cushion time for
restart
0 to 20s
0s
164
First cushion voltage for
restart
0 to 100%
0%
165
Stall prevention
operation level for
restart
0 to 400%
150%
166
Output current
detection signal
retention time
0 to 10s, 9999
0.1s
167
Output current
detection operation
selection
0, 1, 10, 11
0
168
Parameter for manufacturer setting. Do not set.
169
170
Watt-hour meter clear
0, 10, 9999
9999
171
Operation hour meter
clear
0, 9999
9999
172
User group registered
display/batch clear
9999, (0 to 16)
0
173
User group registration 0 to 1999, 9999
9999
174
User group clear
0 to 1999, 9999
9999
Pr.
Name
Setting
range
Initial
value
178
STF terminal function
selection
0 to 20,
22 to 28, 32, 37,
42 to 48,
50 to 53,
57 to 62,
64 to 74,
76 to 80, 85,
87 to 89
92 to 96,
128, 129,
9999
60
179
STR terminal function
selection
61
180
RL terminal function
selection
0
181
RM terminal function
selection
1
182
RH terminal function
selection
2
183
RT terminal function
selection
3
184
AU terminal function
selection
4
185
JOG terminal function
selection
5
186
CS terminal function
selection
6
187
MRS terminal function
selection
24
188
STOP terminal function
selection
25
189
RES terminal function
selection
62
190
RUN terminal function
selection
0 to 8, 10 to 20, 22,
25 to 28, 30 to 36,
38 to 57, 60, 61, 63,
64, 67, 68, 70, 79,
80, 84, 85, 90 to 99,
100 to 108,
110 to 116, 120,
122, 125 to 128,
130 to 136,
138 to 157, 160,
161, 163, 164, 167,
168, 170, 179, 180,
184, 185,
190 to 199,
200 to 208,
211 to 213, 247,
300 to 308,
311 to 313, 347,
9999
0
191
SU terminal function
selection
1
192
IPF terminal function
selection
2
193
OL terminal function
selection
3
194
FU terminal function
selection
4
195
ABC1 terminal function
selection
99
196
ABC2 terminal function
selection
9999
232 to
239
Multi-speed setting (8
speed to 15 speed)
0 to 590Hz, 9999
9999
240
Soft-PWM operation
selection
0, 1
1
241
Analog input display
unit switchover
0, 1
0
242
Terminal 1 added
compensation amount
(terminal 2)
0 to 100%
100%
243
Terminal 1 added
compensation amount
(terminal 4)
0 to 100%
75%
244
Cooling fan operation
selection
0, 1, 101 to 105,
1000, 1001, 1101
to 1105
1
245
Rated slip
0 to 50%, 9999 9999
246
Slip compensation time
constant
0.01 to 10s
0.5s
247
Constant-power range
slip compensation
selection
0, 9999
9999
248
Self power
management selection 0 to 2
0
249
Earth (ground) fault
detection at start
0, 1
0
250
Stop selection
0 to 100s,
1000 to 1100s,
8888, 9999
9999
251
Output phase loss
protection selection
0, 1
1
252
Override bias
0 to 200%
50%
253
Override gain
0 to 200%
150%
254
Main circuit power OFF
waiting time
1 to 3600s,
9999
600s
255
Life alarm status
display
(0 to 255)
0
256
Inrush current limit
circuit life display
(0 to 100%)
100%
257
Control circuit capacitor
life display
(0 to 100%)
100%
258
Main circuit capacitor
life display
(0 to 100%)
100%
259
Main circuit capacitor
life measuring
0, 1, 11
0
260
PWM frequency
automatic switchover
0, 1
1
261
Power failure stop
selection
0 to 2, 11, 12,
21, 22
0
262
Subtracted frequency at
deceleration start
0 to 20Hz
3Hz
263
Subtraction starting
frequency
0 to 590Hz,
9999
60/50Hz
264
Power-failure
deceleration time 1
0 to 3600s
5s
265
Power-failure
deceleration time 2
0 to 3600s,
9999
9999
Pr.
Name
Setting
range
Initial
value
266
Power failure
deceleration time
switchover frequency
0 to 590Hz
60/50Hz
267
Terminal 4 input
selection
0 to 2
0
268
Monitor decimal digits
selection
0, 1, 9999
9999
269
Parameter for manufacturer setting. Do not set.
270
Stop-on contact/load
torque high-speed
frequency control
selection
0 to 3, 11, 13
0
271
High-speed setting
maximum current
0 to 400%
50%
272
Middle-speed setting
minimum current
0 to 400%
100%
273
Current averaging
range
0 to 590Hz,
9999
9999
274
Current averaging filter
time constant
1 to 4000
16
275
Stop-on contact
excitation current low-
speed multiplying factor
0 to 300%, 9999 9999
276
PWM carrier frequency
at stop-on contact
0 to 9, 9999
9999
0 to 4, 9999
278
Brake opening
frequency
0 to 30Hz
3Hz
279
Brake opening current 0 to 400%
130%
280
Brake opening current
detection time
0 to 2s
0.3s
281
Brake operation time at
start
0 to 5s
0.3s
282
Brake operation
frequency
0 to 30Hz
6Hz
283
Brake operation time at
stop
0 to 5s
0.3s
284
Deceleration detection
function selection
0, 1
0
285
Overspeed detection
frequency (Excessive
speed deviation
detection frequency)
0 to 30Hz, 9999 9999
286
Droop gain
0 to 100%
0%
287
Droop filter time constant 0 to 1s
0.3s
288
Droop function
activation selection
0 to 2, 10, 11,
20 to 22
0
289
Inverter output terminal
filter
5 to 50ms, 9999 9999
290
Monitor negative output
selection
0 to 7
0
291
Pulse train I/O selection
0, 1, 10, 11, 20,
21, 100
(FM type)
0
0, 1 (CA type)
292
Automatic acceleration/
deceleration
0, 1, 3, 5 to 8, 11
0
293
Acceleration/deceleration
separate selection
0 to 2
0
294
UV avoidance voltage
gain
0 to 200%
100%
295
Frequency change
increment amount
setting
0, 0.01, 0.10,
1.00, 10.00
0
296
Password lock level
0 to 6, 99,
100 to 106, 199,
9999
9999
297
Password lock/unlock
(0 to 5),
1000 to 9998,
9999
9999
298
Frequency search gain 0 to 32767,
9999
9999
299
Rotation direction
detection selection at
restarting
0, 1, 9999
0
313
DO0 output selection
0 to 8, 10 to 20, 22,
25 to 28, 30 to 36,
38 to 57, 60, 61, 63,
64, 68, 70, 79,
84 to 99, 100 to 108,
110 to 116, 120,
122, 125 to 128,
130 to 136,
138 to 157, 160,
161, 163, 164, 168,
170, 179,
184 to 199,
200 to 208,
211 to 213, 247,
248, 300 to 308,
311 to 313, 347,
348, 9999
9999
314
DO1 output selection
9999
315
DO2 output selection
9999
316
DO3 output selection
9999
317
DO4 output selection
9999
318
DO5 output selection
9999
319
DO6 output selection
9999
320
RA1 output selection
0 to 8, 10 to 20,
22, 25 to 28,
30 to 36,
38 to 57, 60, 61,
63, 64, 68, 70,
79, 80, 84 to 91,
94 to 99,
200 to 208,
211 to 213, 247,
248, 9999
9999
321
RA2 output selection
9999
322
RA3 output selection
9999
328
Inverter/converter
switching
0 to 9999
0
Pr.
Name
Setting
range
Initial
value