5 CC-Link IE Field Network
5.5 Backing up/Restoring Data of Devices Supporting iQSS
127
5
4.
Setting a target device
• Setting a module
When '1H' (module unit) is set for the execution unit in the step of 'Setting the execution unit', set the start I/O number of a
target device for data restoration to SD1439.
• Setting a station number
When '2H' (station unit) or '3H' (station sub-ID unit) is set for the execution unit in the step of 'Setting the execution unit', set
the station number of a target device for data restoration to SD1440.
• Setting a station sub-ID number
When '3H' (station sub-ID unit) is set for the execution unit in the step of 'Setting the execution unit', set the station sub-ID
number of a target device for data restoration to SD1441.
To restore the data of a device supporting iQSS which is connected to a bridge module (NZ2AW1GFAL), set
the ID number of AnyWireASLINK to SD1441.
For details on the ID number (SD1440) of AnyWireASLINK, refer to the following section.
Page 47 Setting the restoration setting
5.
Setting the operation setting when a data restoration error occurs
Set the operation on error to the lower 8 bits of SD1444 in order to in order to restore data for multiple devices supporting
iQSS.
■
Performing a data restoration
Data is restored if SM1439 is turned ON while SD1446 is '1H' (ready).
Once data is restored, SD1446 will be '2H' (being executed).
Check that the other station data link status (SW00B0 to SW00B73) indicates that a data link is in process before performing
a data restoration.
■
Requiring a data restoration cancellation
The data restoration stops if SM1442 is turned ON while SD1446 is '1H' (ready) or '2H' (being executed).
■
Releasing the right to use
When SM1435 is turned ON after a data restoration is completed (including a cancellation or an error), the right to use is
released and the next data restoration is ready to be performed.
SM1435 turns ON to OFF when the right to use is released.
If the right to use is released even though it has already been done, SM1435 remains ON since no processing is performed.
In that case, set SM1435 to OFF.
Target device (Module)
Description
0 to FFH: Start I/O number
When '1H' (module unit) is set for the execution unit, set the value obtained by dividing the start I/O number of a CC-
Link IE Field Network master/local module, which is connected to a target device supporting iQSS, by 16.
Target device (Station
number)
Description
1 to 120: Station number
When '2H' (station unit) or '3H' (station sub-ID unit) is set for the execution unit, set the station number of a target
device supporting iQSS or a device supporting iQSS which is connected to the module with the specified station
number.
Target device (Station sub-ID
number)
Description
0 to 9999: Station sub-ID number
When '3H' (station sub-ID unit) is set for the execution unit, set the station sub-ID number of a target device supporting
iQSS.
Operation on error
Description
0H: Continue
Set this to continue a data restoration even if it fails on some devices while being performed to multiple devices
supporting iQSS.
1H: Stop
Set this to stop a data restoration even if it fails on some devices while being performed to multiple devices supporting
iQSS.
Содержание 13JV28
Страница 1: ...iQ Sensor Solution Reference Manual ...
Страница 2: ......
Страница 166: ...164 6 Ethernet 6 5 Backing up Restoring Data of Devices Supporting iQSS MEMO ...
Страница 185: ...7 AnyWireASLINK 7 4 Backing up Restoring Data of Devices Supporting iQSS 183 7 Sample program ...
Страница 195: ...7 AnyWireASLINK 7 4 Backing up Restoring Data of Devices Supporting iQSS 193 7 Sample program ...
Страница 228: ...226 8 CC Link 8 4 Backing up Restoring Data of Devices Supporting iQSS Sample program ...
Страница 238: ...236 8 CC Link 8 4 Backing up Restoring Data of Devices Supporting iQSS Sample program ...
Страница 244: ...242 8 CC Link 8 4 Backing up Restoring Data of Devices Supporting iQSS Sample program ...
Страница 278: ...276 9 CC Link IE Field Network 9 4 Backing up Restoring Data of Devices Supporting iQSS Sample program ...
Страница 309: ...10 Ethernet 10 5 Backing up Restoring Data of Devices Supporting iQSS 307 10 Sample program ...
Страница 371: ...APPX Appendix 8 Backup File Capacity 369 A MEMO ...
Страница 373: ...I 371 MEMO ...
Страница 377: ......