7 AnyWireASLINK
7.4 Backing up/Restoring Data of Devices Supporting iQSS
187
7
■
Setting the restoration setting
1.
Setting a target module type
Set a target module with the lower 8 bits of SD1362 (iQ Sensor Solution data backup/restoration target module, execution unit
setting).
2.
Setting an execution unit
Set a unit to specify the range of data to be restored at once.
Specify the execution unit to the upper 8 bits of SD1362.
3.
Selecting a folder for data restoration
Set a folder number to SD1363 (iQ Sensor Solution backup/restoration folder number setting).
4.
Setting a target device
• Setting a module
When '1H' (module unit) is set for the execution unit, set a start I/O number to SD1364 (iQ Sensor Solution data backup/
restoration target setting (target module)).
In a multiple CPU system, only the AnyWireASLINK master module controlled by a host CPU can be backed up. Data backup
cannot be performed for non-controlled modules.
• Setting an ID number
When '2H' (ID unit) is set for the execution unit, set an ID number to SD1365 (iQ Sensor Solution data backup/restoration
target setting (target device 1)).
5.
Setting the operation setting when a data restoration error occurs
Set the operation to be performed when the data restoration fails on some devices while being processed to multiple devices
supporting iQSS to the lower 8 bits of SD1367 (iQ Sensor Solution data backup/restoration operation setting).
Target module type
Description
1H: AnyWireASLINK
Set this to specify a device supporting iQSS which is connected to the AnyWireASLINK master module.
Execution unit
Description
1H: Module unit
Set this to specify all devices supporting iQSS which are connected to the AnyWireASLINK master module with
the specified start I/O number.
2H: ID unit
Set this to specify the device supporting iQSS with the specified ID number among the devices which are
connected to the AnyWireASLINK master module with the specified start I/O number.
Target folder
Description
0 to 99: Target folder specification
Specify a number (0 to 99) of the backup folder name to be restored.
Target device (Module)
Description
0 to FFH: Start I/O number
Set the start I/O number (the value obtained by dividing the start I/O number by 16) of the AnyWireASLINK
master module which is connected to a target device supporting iQSS.
Target device (ID number)
Description
0 to 9999: ID number
Set the ID number of a target device supporting iQSS.
Operation on error
Description
0H: Continue
Set this to continue a data restoration even if it fails on some devices.
1H: Stop
Set this to stop a data restoration if it fails on some devices.
Содержание 13JV28
Страница 1: ...iQ Sensor Solution Reference Manual ...
Страница 2: ......
Страница 166: ...164 6 Ethernet 6 5 Backing up Restoring Data of Devices Supporting iQSS MEMO ...
Страница 185: ...7 AnyWireASLINK 7 4 Backing up Restoring Data of Devices Supporting iQSS 183 7 Sample program ...
Страница 195: ...7 AnyWireASLINK 7 4 Backing up Restoring Data of Devices Supporting iQSS 193 7 Sample program ...
Страница 228: ...226 8 CC Link 8 4 Backing up Restoring Data of Devices Supporting iQSS Sample program ...
Страница 238: ...236 8 CC Link 8 4 Backing up Restoring Data of Devices Supporting iQSS Sample program ...
Страница 244: ...242 8 CC Link 8 4 Backing up Restoring Data of Devices Supporting iQSS Sample program ...
Страница 278: ...276 9 CC Link IE Field Network 9 4 Backing up Restoring Data of Devices Supporting iQSS Sample program ...
Страница 309: ...10 Ethernet 10 5 Backing up Restoring Data of Devices Supporting iQSS 307 10 Sample program ...
Страница 371: ...APPX Appendix 8 Backup File Capacity 369 A MEMO ...
Страница 373: ...I 371 MEMO ...
Страница 377: ......