270
9 CC-Link IE Field Network
9.4 Backing up/Restoring Data of Devices Supporting iQSS
■
Setting the restoration setting
1.
Setting a target module type
Set a target module with the lower 8 bits of SD1362 (iQ Sensor Solution data backup/restoration target module, execution unit
setting).
2.
Setting an execution unit
Set a unit to specify the range of data to be restored at once.
Specify the execution unit to the upper 8 bits of SD1362.
3.
Selecting a folder for data restoration
Set a folder number to SD1363 (iQ Sensor Solution backup/restoration folder number setting).
4.
Setting a target device
• Setting a module
When '1H' (module unit) is set for the execution unit, set a start I/O number to SD1364 (iQ Sensor Solution data backup/
restoration target setting (target module)).
In a multiple CPU system, only the CC-Link IE Field Network master station controlled by a host CPU can be restored. Data
restoration cannot be performed for non-controlled modules.
• Setting a station number
When '2H' (station unit) or '3H' (station sub-ID unit) is set for the execution unit, set a station number to SD1365 (iQ Sensor
Solution data backup/restoration target setting (target device 1)).
• Setting a station sub-ID number
When '3H' (station sub-ID unit) is set for the execution unit, set a station sub-ID number to SD1366 (iQ Sensor Solution
backup/restoration target setting (target device 2)).
When backup/restore the data in a device supporting iQSS which is connected to a bridge module
(NZ2AW1GFAL), set the ID number of AnyWireASLINK to SD1366.
Target module type
Description
4H: CC-Link IE Field Network
Set this to specify a device supporting iQSS which is connected to the CC-Link IE Field Network master station.
Execution unit
Description
1H: Module unit
Set this to specify the device supporting iQSS which is connected to the own network among the devices which
are connected to a CC-Link IE Field Network master station with the specified start I/O number.
2H: Station unit
Set this to specify either of the following iQSS supported devices which are connected to a CC-Link IE Field
Network master station with the specified start I/O number: the devices supporting iQSS with the specified
station number or all the devices supporting iQSS which are connected to the specified station number.
3H: Station sub-ID unit
Set this to specify the following devices supporting iQSS which are connected to a CC-Link IE Field Network
master station with the specified start I/O number: the devices which are connected to the specified station
number with the specified station sub-ID number.
Target folder
Description
0 to 99: Target folder specification
Specify a number (0 to 99) of the backup folder name to be restored.
Target device (Module)
Description
0 to FFH: Start I/O number
Set the start I/O number (the value obtained by dividing the start I/O number by 16) of the CC-Link IE Field
Network master station which is connected to a target device supporting iQSS.
Target device (Station number)
Description
1 to 120: Station number
Set the station number of a target device supporting iQSS or the station number of the module which is
connected to a device supporting iQSS.
Target device (Station sub-ID
number)
Description
0 to 9999: Station sub-ID number
Set the station sub-ID number of a target device supporting iQSS.
Содержание 13JV28
Страница 1: ...iQ Sensor Solution Reference Manual ...
Страница 2: ......
Страница 166: ...164 6 Ethernet 6 5 Backing up Restoring Data of Devices Supporting iQSS MEMO ...
Страница 185: ...7 AnyWireASLINK 7 4 Backing up Restoring Data of Devices Supporting iQSS 183 7 Sample program ...
Страница 195: ...7 AnyWireASLINK 7 4 Backing up Restoring Data of Devices Supporting iQSS 193 7 Sample program ...
Страница 228: ...226 8 CC Link 8 4 Backing up Restoring Data of Devices Supporting iQSS Sample program ...
Страница 238: ...236 8 CC Link 8 4 Backing up Restoring Data of Devices Supporting iQSS Sample program ...
Страница 244: ...242 8 CC Link 8 4 Backing up Restoring Data of Devices Supporting iQSS Sample program ...
Страница 278: ...276 9 CC Link IE Field Network 9 4 Backing up Restoring Data of Devices Supporting iQSS Sample program ...
Страница 309: ...10 Ethernet 10 5 Backing up Restoring Data of Devices Supporting iQSS 307 10 Sample program ...
Страница 371: ...APPX Appendix 8 Backup File Capacity 369 A MEMO ...
Страница 373: ...I 371 MEMO ...
Страница 377: ......