360
APPX
Appendix 6 Special Relay (SM)/Special Register (SD) List
SD1452
iQ Sensor Solution
backup/restoration error
cause in a module
Storing the cause of the
data backup/restoration
error detected in a
module
This register stores the cause of the data backup/restoration error
detected in a module.
When errors are detected in multiple devices, the error detected first is
stored.
A value is cleared to '0' when the right-to-use is acquired.
For details on the stored error cause, refer to the following section.
•
MELSEC-L CPU Module User's Manual (Hardware Design,
Maintenance and Inspection)
•
QCPU User's Manual (Hardware Design, Maintenance and
Inspection)
•
User's manual for the data backup/restoration target module
S (status
change/error)
SD1453
iQ Sensor Solution
backup/restoration error
cause in a device
Storing the cause of the
data backup/restoration
error detected in a device
This register stores the cause of the data backup/restoration error
detected in a target device.
When errors are detected in multiple devices, the error detected first is
stored.
A value is cleared to '0' when the right-to-use is acquired.
For details on the stored error cause, refer to the following section.
•
•
User's manual for the data backup/restoration target module
S (status
change/error)
SD1454
iQ Sensor Solution
backup/restoration error
module/execution unit
information
Storing the information of
target module/execution
unit when data backup/
restoration error occurred
This register stores the target module type and execution unit
information when a data backup/restoration error occurred.
■
Lower 8 bits (target module type)
• 1H: AnyWireASLINK
• 2H: CC-Link
• 3H: Ethernet
• 4H: CC-Link IE Field Network
■
Upper 8 bits (execution unit)
<AnyWireASLINK>
• 1H: Module unit
• 2H: ID unit
<CC-Link, CC-Link IE Field Network>
• 1H: Module unit
• 2H: Station unit
• 3H: Station sub-ID unit
<Ethernet>
• 1H: Module unit
• 2H: IP address unit
When errors are detected in multiple devices, the information of the
device where the error is detected first is stored.
A value is cleared to '0' when the right-to-use is acquired.
S (status
change/error)
SD1455
iQ Sensor Solution
backup/restoration error
folder number
information
Storing the target folder
number when a data
backup/restoration error
occurred
This register stores the target folder number (0 to 99) when a data
backup/restoration error occurred.
If the folder number cannot be identified, 'FFFFH' will be stored.
A value is cleared to '0' when the right-to-use is acquired.
S (status
change/error)
SD1456
iQ Sensor Solution
backup/restoration error
module information
Storing the information of
the target device (target
module) where a data
backup/restoration error
is detected first
This register stores the information of the target device (target module)
where a data backup/restoration error occurred.
• Start I/O No.
: Module
• 03FFH: Built-in Ethernet
When errors are detected in multiple devices, the information of the
target device (target module) where the error is detected first is stored.
A value is cleared to '0' when the right-to-use is acquired.
S (status
change/error)
SD1457
iQ Sensor Solution
backup/restoration error
device information
(target device 1)
Storing the information of
the target device where a
data backup/restoration
error is detected first
This register stores the information of the device (target device 1)) where
a data backup/restoration error occurred.
<AnyWireASLINK>
• ID number
<CC-Link, CC-Link IE Field Network>
• Station number
<Ethernet>
• IP address (lower 16 bits)
When errors are detected in multiple devices, the information of the
device (target device 1) where the error is detected first is stored.
A value is cleared to '0' when the right-to-use is acquired.
S (status
change/error)
Number
Name
Description
Details
Set by
(setting
timing)
Содержание 13JV28
Страница 1: ...iQ Sensor Solution Reference Manual ...
Страница 2: ......
Страница 166: ...164 6 Ethernet 6 5 Backing up Restoring Data of Devices Supporting iQSS MEMO ...
Страница 185: ...7 AnyWireASLINK 7 4 Backing up Restoring Data of Devices Supporting iQSS 183 7 Sample program ...
Страница 195: ...7 AnyWireASLINK 7 4 Backing up Restoring Data of Devices Supporting iQSS 193 7 Sample program ...
Страница 228: ...226 8 CC Link 8 4 Backing up Restoring Data of Devices Supporting iQSS Sample program ...
Страница 238: ...236 8 CC Link 8 4 Backing up Restoring Data of Devices Supporting iQSS Sample program ...
Страница 244: ...242 8 CC Link 8 4 Backing up Restoring Data of Devices Supporting iQSS Sample program ...
Страница 278: ...276 9 CC Link IE Field Network 9 4 Backing up Restoring Data of Devices Supporting iQSS Sample program ...
Страница 309: ...10 Ethernet 10 5 Backing up Restoring Data of Devices Supporting iQSS 307 10 Sample program ...
Страница 371: ...APPX Appendix 8 Backup File Capacity 369 A MEMO ...
Страница 373: ...I 371 MEMO ...
Страница 377: ......