260
9 CC-Link IE Field Network
9.4 Backing up/Restoring Data of Devices Supporting iQSS
■
Setting the backup setting
1.
Setting a target module type
Set a target module with the lower 8 bits of SD1362 (iQ Sensor Solution data backup/restoration target module, execution unit
setting).
2.
Setting an execution unit
Set a unit to specify the range of data to be backed up at once.
Specify the execution unit to the upper 8 bits of SD1362.
3.
Setting a number for a data backup folder name
Set a folder number to SD1363 (iQ Sensor Solution backup/restoration folder number setting).
*1 When the specified folder number exists, the operation to be performed depends on the specification of the execution unit as follows:
Target module type
Description
4H: CC-Link IE Field Network
Set this to specify a device supporting iQSS which is connected to the CC-Link IE Field Network master station.
Execution unit
Description
1H: Module unit
Set this to specify the device supporting iQSS which is connected to the own network among the devices which
are connected to a CC-Link IE Field Network master station with the specified start I/O number.
2H: Station unit
Set this to specify either of the following iQSS supported devices which are connected to a CC-Link IE Field
Network master station with the specified start I/O number: the devices supporting iQSS with the specified
station number or all devices supporting iQSS which are connected to the specified station number.
3H: Station sub-ID unit
Set this to specify the following devices supporting iQSS which are connected to a CC-Link IE Field Network
master station with the specified start I/O number: the devices which are connected to the specified station
number with the specified station sub-ID number.
Target folder
Description
FFFFH: Automatic specification (default)
Among the numbers (0 to 99) that are not used for backup folder names, the smallest number is used for a new
backup folder name.
An error occurs when unused number is no longer available due to such cases as the number of folders reached
the upper limit.
FFFEH: Automatic specification (folder
deletion supported)
Among the numbers (0 to 99) that are not used for backup folder names, the smallest number is used for a new
backup folder name.
The oldest backup folder (date_number) is deleted and the number of the deleted folder is used for a new backup
folder name when unused number is no longer available due to such cases as the number of folders reached the
upper limit.
0 to 99: Target folder specification
Specify a number (0 to 99) of the backup folder name.
When another folder with the same number exists, the target data is overwritten in execution unit without
changing the folder name.
Execution unit
Operation
1H: Module unit
When the backup data with the same target module exists, the backup folder (start I/O number_station number)
is deleted before performing data backup.
2H: Station unit
When the backup data with the same target module and the same target station number exists, data backup is
performed after the backup folder (start I/O number_station number) is deleted.
3H: Station sub-ID unit
When the backup data with the same target module and the same target station number exists, the information of
the backed up station sub-ID is added to the system file for iQ Sensor Solution backup/restoration.
When the backup data with the same target module, the same target station number, and the same target station
sub-ID number exists, the backup data (information of each station sub-ID) is deleted before performing data
backup.
Содержание 13JV28
Страница 1: ...iQ Sensor Solution Reference Manual ...
Страница 2: ......
Страница 166: ...164 6 Ethernet 6 5 Backing up Restoring Data of Devices Supporting iQSS MEMO ...
Страница 185: ...7 AnyWireASLINK 7 4 Backing up Restoring Data of Devices Supporting iQSS 183 7 Sample program ...
Страница 195: ...7 AnyWireASLINK 7 4 Backing up Restoring Data of Devices Supporting iQSS 193 7 Sample program ...
Страница 228: ...226 8 CC Link 8 4 Backing up Restoring Data of Devices Supporting iQSS Sample program ...
Страница 238: ...236 8 CC Link 8 4 Backing up Restoring Data of Devices Supporting iQSS Sample program ...
Страница 244: ...242 8 CC Link 8 4 Backing up Restoring Data of Devices Supporting iQSS Sample program ...
Страница 278: ...276 9 CC Link IE Field Network 9 4 Backing up Restoring Data of Devices Supporting iQSS Sample program ...
Страница 309: ...10 Ethernet 10 5 Backing up Restoring Data of Devices Supporting iQSS 307 10 Sample program ...
Страница 371: ...APPX Appendix 8 Backup File Capacity 369 A MEMO ...
Страница 373: ...I 371 MEMO ...
Страница 377: ......