MIOX RIO Zuni™ Operators Manual
P/N: 102-00094-I
Page 9
Hydrogen Vents
Upward-sloping piping connected to outside environment for venting potentially dangerous
hydrogen gas (See Hydrogen Safety White Paper).
Level Switch Assembly
Assembly of two level switches and a level switch cable. The level switches control the OSG
when installed in the oxidant tank. The 15’ cable connects the level switches to the OSG.
See Figure 2 for details. Note: The level switches are orientation-sensitive and must be
installed with the arrow pointing upward in order to function properly.
System Cover
A rigid plastic housing that covers and protects the key components of the RIO Zuni.
LCD Display
Visual Display with a cycling menu of system status and operational parameters. See Figure
3 for details.
LED Indicator
A multi-color LED which displays system status. See Figure 3 for details.
Electrical Enclosure
An actively-cooled aluminum box housing the control board, power supplies and other
electronic components of the RIO Zuni System. See Figure 3 for details.
Brine Pump
An automated peristaltic pump which controls the system’s brine flowrate and acts as a
check valve to prevent brine supply dilution. Capable of withstanding up to 10 PSI of
pressure. See Figure 3 for details.
Water Pump
An automated peristaltic pump which controls the overall system flowrate and acts as a
check valve to prevent oxidant from flowing into the water supply. Capable of withstanding
up to 10 PSI of pressure. See Figure 3 for details.
MIOX Zuni Electrolytic Cell
A proprietary electrolytic cell manufactured by MIOX produces 1.0 lbs of FAC per day of
runtime. 1 lb. RIO Zuni OSGs use one cell while 2 lb. RIO Zuni OSGs use two cells. See
Figure 4 for details.
Thermowells
In-line temperature sensors used to evaluate operational efficiency of the system. See
Figure 4 for details.
Electrical Back Panel
All of the unit’s electrical connections, including the power switch, system fuse, IEC power
receptacle, and connectors for the Level Switch Assembly, a USB jump drive, and an
Ethernet cable. See Figure 5 for details.
Содержание RIO Zuni 1
Страница 18: ...MIOX RIO Zuni Operators Manual P N 102 00094 I Page 18 Figure 8 RIO Zuni Connections...
Страница 35: ...MIOX RIO Zuni Operators Manual P N 102 00094 I Page 35...
Страница 36: ...MIOX RIO Zuni Operators Manual P N 102 00094 I Page 36...
Страница 37: ...MIOX RIO Zuni Operators Manual P N 102 00094 I Page 37...
Страница 38: ...MIOX RIO Zuni Operators Manual P N 102 00094 I Page 38...
Страница 39: ...MIOX RIO Zuni Operators Manual P N 102 00094 I Page 39...