32

  Maintenance Precautions

1

 

The accuracy could change by 2 to 3% when the piping is 

removed or replaced.

2

 

Do not insert a stick or wire into the piping ports.

3

 

Do not touch the terminals or connectors when power is 

on.

  Installation Precautions

1

 

Ensure the flow direction of the fluid.

  Please follow the flow direction indicator for installation and 

piping.

2

 

Flush out all dirt and dust by air blow before connect the 

piping to the sensor.

3

 

Do not drop or hit.

  When installation, do not drop, hit or apply excessive shock 

(100m/s

2

). Internal damage can cause malfunction even if the 

housing appears to be undamaged.

4

 

Do not install multiple products in close proximity.

  The heat generated from each product could cause the 

temperature to rise and change the characteristics of product 
or deterioration of the plastic parts. Please set the products 
10mm apart from each other.

5

 

Hold the sensor body when installing.

  The tensile strength of the cable is 24.5 N and apply excessive 

pulling force can cause damage to the sensor.

 

CAUTION

  Installation Precautions

1

 

Please follow the specified tightening torque.

 

Over tighten will damage the product.

2

 

Do not mount the sensor in a place that will be used as a 

foothold.

  The product may damage if sit or step on it accidentally. 

3

 

When mounting without a bracket, please use P type self-

tapping screw- M3×L 6mm.

4

 

Do not remove the fixed pin for the One-Touch Fitting.

  To avoid losing the internal parts and cause malfunction.

5

 

Please do not replace fittings by yourself.

6

  While installing the KFP01-101/201 to the pipe, please apply 

air tube with I.D. 5 mm.

 

While installing the KFP01-005/010/050/100/500 to the pipe, 
please apply air tube with I.D. 4 mm.

  Other Precautions

1

 

After power is supplied, the output will remain off until the 

display is turned on. Please operate the sensor after the 

value is shown.

2

 

Stop the control systems before perform setting changes.

  During the initial flow and pressure setting, the product will 

switch the output according to the existing settings until the 
changes are complete.

 

WARNING

  Fluid

1

 

Check the regulator and flow adjustment valve before 

introducing the fluid.

 

If the pressure or flow rate exceeded the specified range, the 
sensing element may be damaged.

2

 

The sensing element cannot measure properly if foreign 

matter adheres to it.

3

 

On the inlet side, be sure to install an air filter below the 

filtration level of 10um.

4

 

Recommended Equipments and Installation

NOTE

 

When measuring the pressure of the inlet side, install a throttle valve or 

solenoid valve on the outlet side.

 

When measuring the pressure of the outlet side, install a throttle valve 

or solenoid valve on the inlet side.

5

 

Recommended Equipments and Installation Example

NOTE

 

When measuring the pressure of the 

 

inlet side, install a throttle valve or 

 

solenoid valve on the outlet side.

NOTE

 

When measuring the pressure of the 

 

outlet side, install a throttle valve or 

 

solenoid valve on the inlet side.

  Disclaimer

1

 Our warranty applies solely to our product, not to any other 

damages and injuries which occur by earthquakes, fires, 
the acts by third party, other matters, acts intentionally, acts 
accidentally, misuse, or other abnormal conditions that are not 
the responsible of Mindman.

2

 Our warranty applies solely to our product, not to any ther 

additional damages (the loses of business profits, business 
interruption, etc.) incurred due to using or misusing the 
product.

3

 Our warranty excludes any injuries and damages happened by 

using the product beyond the specified range of catalog or/and 
not following the instruction manual.

Air

Source

Air 

Dryer

Filter Regulator

Flow Sensor

MFP01 Series

Pressure sensor

Micro Mist 

Separator

(Oil Mist Filiter)

Outlet

Inlet

Air

Source

Air 

Dryer

Filter Regulator

Flow Sensor

MFP01 Series

Throttle

Valve

or

Micro Mist 

Separator

(Oil Mist 

Filiter)

Pressure sensor

Outlet

Inlet

Air

Source

Air 

Dryer

Filter Regulator

Flow Sensor

MFP01 Series

Throttle

Valve

Micro Mist 

Separator

(Oil Mist Filiter)

Pressure sensor

Outlet

Inlet

or

Caution for safety

FLOW & PRESSURE SENSOR 

( INSTRUCTION MANUAL )

Содержание MFP01 Series

Страница 1: ...Flow Pressure Sensor INSTRUCTION MANUAL MFP01 series 210107...

Страница 2: ...g selection 19 F 03 LCD display color selection 19 F 04 Response time selection 19 F 05 Display refresh time selection 20 F 06 Unit selection 21 F 07 Flow reference standard selection 22 F 08 Display...

Страница 3: ...STRUCTION MANUAL MFP01 Product features Cost Control User friendly High Performance High Precision Cost Reduction Traditional 2 Sensor cost 2 Power supply 2 Plumbing costs Time 2 Wiring work cost Time...

Страница 4: ...lue Pressure value NPN output PNP output Voltage output 1 5V Current output 4 20 mA 50ms pulse output FLOW PRESSURE SENSOR INSTRUCTION MANUAL MFP01 Product features 2 in 1 Design Pressure and flow rat...

Страница 5: ...NUAL MFP01 Application Application 01 Paint and coating flow monitoring Air flow and pressure management of paint and coating processes Application 02 Laser welding monitoring Precision management of...

Страница 6: ...on state of micro electronic parts by flow rate Application 05 Leakage detect Container with gas and inspect whether it leaks Application 04 Electronic part installation Control the tension of gold wi...

Страница 7: ...ins the inlet side is cooled by the flow the outlet side is warmed by the heat of the inlet side of the heater and the temperature distribution is like b c Large flow When the flow increases it become...

Страница 8: ...ut Accumulated Pulse Output Pressure One Point Set Mode Hysteresis Mode Window Comparator Mode Hysteresis Adjustable Output short circuit proterction Yes Accumulated pulse output 1 5 mL Pulse 10 mL Pu...

Страница 9: ...ut to malfunction Window comparator mode Window comparator mode Accumulated output mode Accumulated output mode Flow pressure FH 1 FH 2 H 1 H 2 FL 1 FL 2 L 1 L 2 ON OFF Flow pressure FH 1 FH 2 H 1 H 2...

Страница 10: ...6 4 2 0 12 10 8 6 4 2 0 0 018 0 016 0 014 0 012 0 010 0 008 0 006 0 004 0 002 0 0 1 MPa 0 1 MPa 0 1 MPa 0 1 MPa 0 1 MPa 0 2 MPa 0 3 0 35 0 4 MPa 0 5 MPa 0 2 MPa 0 2 MPa 0 2 MPa 0 2 MPa 0 2 MPa 0 3 MP...

Страница 11: ...e to the product Piping for the One Touch Fitting insert the tube firmly into the fitting and make sure it cannot be pulled out Also using the proper tube cutter is recommended to ensure square edge t...

Страница 12: ...Output 2 Blue Power supply Orange Analog output Brown Power supply Main Circuit Load Load Orange RS 485 B Yellow RS 485 A Black Output 1 White Output 2 Blue Power supply Brown Power supply Main Circui...

Страница 13: ...nal Thread Rc1 4 Rc1 8 Quick fitting 6 8 2 2 5 5 5 depth 2 2 5 5 5 depth 36 7 36 7 9 5 9 5 18 28 28 18 55 55 24 24 3 3 8 50 2 50 2 17 17 52 52 A B Code Tube I D A mm 8 92 2 6 83 Code Thread B mm Rc1 8...

Страница 14: ...25 3 5 9 25 8 5 59 8 40 MFP01 Mounting accessories Mounting bracket Panel type MP A26 Front protective lid Panel adapter Panel adapter Panel adapter Front protective lid Panel adapter MP C4 Panel thic...

Страница 15: ...g Signal Indicator Pressure symbol Pressure display Pressure Unit Display Section Flow Unit Display Section Flow Symbol Analog Signal Indicator Output 1 Indicator Output 2 Indicator Flow Display Setti...

Страница 16: ...board 3 Sensor SiC 4 Liquid crystal cover PC 5 Liquid crystal 6 Button Silicone 7 Port Filter Stainless Steel No Part name Material 8 Resin Body PBT 9 O ring Viton 10 O ring NBR 11 Quick Fitting 12 O...

Страница 17: ...de KY5 oUt2 OUT2 output type no FL 2 OUT2 set value input 50 of maximum measured flow rate 005 250 mL min 010 500 mL min 050 2 50 L min 100 5 00 L min 500 25 0 L min 101 50 0 L min 201 100 L min FK 2...

Страница 18: ...sion format 1d ID number setting 1 rAt Baud rate setting 96 9600 Bd For Transmission format setting n81 trR Communications protocol setting rtU F 94 F1nE Fine adjustment setting F1nE The displayed val...

Страница 19: ...put Type Setting Press or button to select flow sensor of OUT1 Press or button to select output mode of OUT1 Out1 set value setting Press or button to adjust the set value Fixed hysteresis setting Pre...

Страница 20: ...ed Hysteresis Setting Output Type Setting Press or button to select pressure sensor of OUT1 Press or button to select output mode of OUT1 Out1 set value setting Press or button to adjust the set value...

Страница 21: ...turn to Function Selection Mode DjSP oUt1 L min kPa Ag rESP FLoY L min kPa Ag FLoY 800 L min kPa Ag FLoY 1500 L min kPa Ag FLoY 400 L min kPa Ag F 04 rESP L min kPa Ag FLoY 800 L min kPa Ag CoL SoG L...

Страница 22: ...utton to response time Press or button to select refresh time 7 Response time selections include 50ms 80ms 120ms 200ms 400ms 800ms 1500ms 3 display refresh time selections include 200ms 500ms 1000ms 2...

Страница 23: ...ion Press or button to select the pressure sensor 200ms 500ms 1000ms 500 UPDR L min kPa Ag 200 UPDR L min kPa Ag 1000 UPDR L min kPa Ag Press button F 06 Unit selection Select the flow unit and pressu...

Страница 24: ...Pr oFF L min kPa Ag EEPr 2Aun L min kPa Ag EEPr oFF L min kPa Ag EEPr 5Aun L min kPa Ag AnG FLoY L min kPa Ag AnG PrES L min kPa Ag AnG FLoY L min kPa Ag rEFE nor L min kPa Ag rEFE Anr L min kPa Ag F...

Страница 25: ...button at function selection mode to display F 91 ECo Power save Mode Selected Mode Power Save Mode Selection Press or button to turn on the power save mode Power save mode OFF Power save mode ON NOTE...

Страница 26: ...ing Baud rate Set value Baud Rate Setting Press or button to set baud rate 9600 Bd 19200 Bd 38400 Bd NOTE This function only available for output specification 02 and 04 Transmission Format Set value...

Страница 27: ...t Setting Fine Adjustment Setting Fine Adjustment of Instantaneous Flow Rate Value Fine Adjustment of Pressure Value Return to the measurement mode Return to the measurement mode Press or button to se...

Страница 28: ...Reset to The Default Setting Press or button to return to the factory default setting Disable Enable Press button Measurement mode Pressure value return zero To release holding the button to return me...

Страница 29: ...play zero And release holding the button to return measurement mode 300 0 08 L min kPa Ag bo HoLD L min kPa Ag 20 0 00 L min kPa Ag 300 0 08 L min kPa Ag LoC off L min kPa Ag LoC on L min kPa Ag LoC o...

Страница 30: ...R Normal condition Read Write 000BH Flow sensor display mode 0 Instantaneous flow 1 Accumulated flow Read Write 000CH Accumulated value hold 0 None 1 2 min times 2 5 min times Read Write Error code Ex...

Страница 31: ...C mode Read Write 0026H Flow setting value FL 2 Read Write 0027H Flow setting value FH 2 Read Write 0028H Flow setting value ADL2 Read Write Error code Explanation Operation 0029H Flow setting value A...

Страница 32: ...orm the zero clear function again under no pressure conditions System error Er4 kPa Er4 L min Ag Memory error Turn power off and then restart If error condition remains please return to factory for in...

Страница 33: ...e voltages if using near the sensor will cause the internal circuit components to deteriorate and cause damages 3 Sensors can not withstand lightning strikes The product is CE compliant but can not re...

Страница 34: ...pressure setting the product will switch the output according to the existing settings until the changes are complete WARNING Fluid 1 Check the regulator and flow adjustment valve before introducing...

Отзывы: