29

FLOW & PRESSURE SENSOR 

( INSTRUCTION MANUAL )

MFP01 

Modbus RTU instruction

Error code

Explanation

Operation

0018H

OUT1 output mode

Read /

Write

FLOW

0 : HYS

1 : WIN

2 : ADD

3 : PLS

PRESSURE

0: OPS

1: HYS

2: WIN

0019H

OUT1 output type

0 : N.O. mode

1 : N.C. mode

Read /

Write

001AH

Flow setting value FL-1

Read /

Write

001BH

Flow setting value FH-1

Read /

Write

001CH

Flow setting value ADL1

Read /

Write

001DH

Flow setting value ADH1

Read /

Write

001EH

Fixed hysteresis setting for flow

value HYS

0 ~ 8

Read /

Write

001FH

Pressure setting value

P-1 or L-1

Read /

Write

0020H

Pressure setting value H-1

Read /

Write

0021H

Fixed hysteresis setting for

pressure value HYS

0 ~ 8

Read /

Write

0022H

OUT1 switch

0 : OFF

1 : ON

Read

0023H

OUT2 corresponding sensor

0 : FLOW SENSOR

1 : PRESSURE SENSOR

Read /

Write

0024H

OUT2 output mode

Read /

Write

FLOW

0 : HYS

1 : WIN

2 : ADD

PRESSURE

0: OPS

1: HYS

2: WIN

Read /

Write

0025H

OUT2 output type

0 : N.O. mode

1 : N.C. mode

Read /

Write

0026H

Flow setting value FL-2

Read /

Write

0027H

Flow setting value FH-2

Read /

Write

0028H

Flow setting value ADL2

Read /

Write

Error code

Explanation

Operation

0029H

Flow setting value ADH2

Read /

Write

002AH

Fixed hysteresis setting for flow

value HYS

0 ~ 8

Read /

Write

002BH

Pressure setting value P-2 or L-2

Read /

Write

002CH

Pressure setting value H-2

Read /

Write

002DH

Fixed hysteresis setting for

pressure value HYS

0 ~ 8

Read /

Write

002EH

OUT2 switch

0 : OFF

1 : ON

Read

002FH

Color display for OUT1 or OUT2

selection

0 : OUT1

1 : OUT2

Read /

Write

0030H

Display color setting

0 : SOG ( Switch on Green )

1 : SOR ( Switch on Red )

2 : GRN ( Always is Green )

3 : RED ( Always is Red )

Read /

Write

0031H

Power-save mode

0 : NO

1 : YES

Read /

Write

0032H

Reset to the default setting

0: RECALL

Write

0033H

Instant flow zero adjustment

0 : When over ± 5 %, error code

03H will show

Write

0034H

Pressure zero adjustment

0 : When over ± 3 %, error code

03H will show

Write

0035H

Reset accumulated flow

0 : Accumulated flow value

return to zero

Write

0036H

Key lock / unlock setting

0 : OFF

1 : ON

Read /

Write

0037H

Switch output

0 : NPN

1 : PNP

Read

Содержание MFP01 Series

Страница 1: ...Flow Pressure Sensor INSTRUCTION MANUAL MFP01 series 210107...

Страница 2: ...g selection 19 F 03 LCD display color selection 19 F 04 Response time selection 19 F 05 Display refresh time selection 20 F 06 Unit selection 21 F 07 Flow reference standard selection 22 F 08 Display...

Страница 3: ...STRUCTION MANUAL MFP01 Product features Cost Control User friendly High Performance High Precision Cost Reduction Traditional 2 Sensor cost 2 Power supply 2 Plumbing costs Time 2 Wiring work cost Time...

Страница 4: ...lue Pressure value NPN output PNP output Voltage output 1 5V Current output 4 20 mA 50ms pulse output FLOW PRESSURE SENSOR INSTRUCTION MANUAL MFP01 Product features 2 in 1 Design Pressure and flow rat...

Страница 5: ...NUAL MFP01 Application Application 01 Paint and coating flow monitoring Air flow and pressure management of paint and coating processes Application 02 Laser welding monitoring Precision management of...

Страница 6: ...on state of micro electronic parts by flow rate Application 05 Leakage detect Container with gas and inspect whether it leaks Application 04 Electronic part installation Control the tension of gold wi...

Страница 7: ...ins the inlet side is cooled by the flow the outlet side is warmed by the heat of the inlet side of the heater and the temperature distribution is like b c Large flow When the flow increases it become...

Страница 8: ...ut Accumulated Pulse Output Pressure One Point Set Mode Hysteresis Mode Window Comparator Mode Hysteresis Adjustable Output short circuit proterction Yes Accumulated pulse output 1 5 mL Pulse 10 mL Pu...

Страница 9: ...ut to malfunction Window comparator mode Window comparator mode Accumulated output mode Accumulated output mode Flow pressure FH 1 FH 2 H 1 H 2 FL 1 FL 2 L 1 L 2 ON OFF Flow pressure FH 1 FH 2 H 1 H 2...

Страница 10: ...6 4 2 0 12 10 8 6 4 2 0 0 018 0 016 0 014 0 012 0 010 0 008 0 006 0 004 0 002 0 0 1 MPa 0 1 MPa 0 1 MPa 0 1 MPa 0 1 MPa 0 2 MPa 0 3 0 35 0 4 MPa 0 5 MPa 0 2 MPa 0 2 MPa 0 2 MPa 0 2 MPa 0 2 MPa 0 3 MP...

Страница 11: ...e to the product Piping for the One Touch Fitting insert the tube firmly into the fitting and make sure it cannot be pulled out Also using the proper tube cutter is recommended to ensure square edge t...

Страница 12: ...Output 2 Blue Power supply Orange Analog output Brown Power supply Main Circuit Load Load Orange RS 485 B Yellow RS 485 A Black Output 1 White Output 2 Blue Power supply Brown Power supply Main Circui...

Страница 13: ...nal Thread Rc1 4 Rc1 8 Quick fitting 6 8 2 2 5 5 5 depth 2 2 5 5 5 depth 36 7 36 7 9 5 9 5 18 28 28 18 55 55 24 24 3 3 8 50 2 50 2 17 17 52 52 A B Code Tube I D A mm 8 92 2 6 83 Code Thread B mm Rc1 8...

Страница 14: ...25 3 5 9 25 8 5 59 8 40 MFP01 Mounting accessories Mounting bracket Panel type MP A26 Front protective lid Panel adapter Panel adapter Panel adapter Front protective lid Panel adapter MP C4 Panel thic...

Страница 15: ...g Signal Indicator Pressure symbol Pressure display Pressure Unit Display Section Flow Unit Display Section Flow Symbol Analog Signal Indicator Output 1 Indicator Output 2 Indicator Flow Display Setti...

Страница 16: ...board 3 Sensor SiC 4 Liquid crystal cover PC 5 Liquid crystal 6 Button Silicone 7 Port Filter Stainless Steel No Part name Material 8 Resin Body PBT 9 O ring Viton 10 O ring NBR 11 Quick Fitting 12 O...

Страница 17: ...de KY5 oUt2 OUT2 output type no FL 2 OUT2 set value input 50 of maximum measured flow rate 005 250 mL min 010 500 mL min 050 2 50 L min 100 5 00 L min 500 25 0 L min 101 50 0 L min 201 100 L min FK 2...

Страница 18: ...sion format 1d ID number setting 1 rAt Baud rate setting 96 9600 Bd For Transmission format setting n81 trR Communications protocol setting rtU F 94 F1nE Fine adjustment setting F1nE The displayed val...

Страница 19: ...put Type Setting Press or button to select flow sensor of OUT1 Press or button to select output mode of OUT1 Out1 set value setting Press or button to adjust the set value Fixed hysteresis setting Pre...

Страница 20: ...ed Hysteresis Setting Output Type Setting Press or button to select pressure sensor of OUT1 Press or button to select output mode of OUT1 Out1 set value setting Press or button to adjust the set value...

Страница 21: ...turn to Function Selection Mode DjSP oUt1 L min kPa Ag rESP FLoY L min kPa Ag FLoY 800 L min kPa Ag FLoY 1500 L min kPa Ag FLoY 400 L min kPa Ag F 04 rESP L min kPa Ag FLoY 800 L min kPa Ag CoL SoG L...

Страница 22: ...utton to response time Press or button to select refresh time 7 Response time selections include 50ms 80ms 120ms 200ms 400ms 800ms 1500ms 3 display refresh time selections include 200ms 500ms 1000ms 2...

Страница 23: ...ion Press or button to select the pressure sensor 200ms 500ms 1000ms 500 UPDR L min kPa Ag 200 UPDR L min kPa Ag 1000 UPDR L min kPa Ag Press button F 06 Unit selection Select the flow unit and pressu...

Страница 24: ...Pr oFF L min kPa Ag EEPr 2Aun L min kPa Ag EEPr oFF L min kPa Ag EEPr 5Aun L min kPa Ag AnG FLoY L min kPa Ag AnG PrES L min kPa Ag AnG FLoY L min kPa Ag rEFE nor L min kPa Ag rEFE Anr L min kPa Ag F...

Страница 25: ...button at function selection mode to display F 91 ECo Power save Mode Selected Mode Power Save Mode Selection Press or button to turn on the power save mode Power save mode OFF Power save mode ON NOTE...

Страница 26: ...ing Baud rate Set value Baud Rate Setting Press or button to set baud rate 9600 Bd 19200 Bd 38400 Bd NOTE This function only available for output specification 02 and 04 Transmission Format Set value...

Страница 27: ...t Setting Fine Adjustment Setting Fine Adjustment of Instantaneous Flow Rate Value Fine Adjustment of Pressure Value Return to the measurement mode Return to the measurement mode Press or button to se...

Страница 28: ...Reset to The Default Setting Press or button to return to the factory default setting Disable Enable Press button Measurement mode Pressure value return zero To release holding the button to return me...

Страница 29: ...play zero And release holding the button to return measurement mode 300 0 08 L min kPa Ag bo HoLD L min kPa Ag 20 0 00 L min kPa Ag 300 0 08 L min kPa Ag LoC off L min kPa Ag LoC on L min kPa Ag LoC o...

Страница 30: ...R Normal condition Read Write 000BH Flow sensor display mode 0 Instantaneous flow 1 Accumulated flow Read Write 000CH Accumulated value hold 0 None 1 2 min times 2 5 min times Read Write Error code Ex...

Страница 31: ...C mode Read Write 0026H Flow setting value FL 2 Read Write 0027H Flow setting value FH 2 Read Write 0028H Flow setting value ADL2 Read Write Error code Explanation Operation 0029H Flow setting value A...

Страница 32: ...orm the zero clear function again under no pressure conditions System error Er4 kPa Er4 L min Ag Memory error Turn power off and then restart If error condition remains please return to factory for in...

Страница 33: ...e voltages if using near the sensor will cause the internal circuit components to deteriorate and cause damages 3 Sensors can not withstand lightning strikes The product is CE compliant but can not re...

Страница 34: ...pressure setting the product will switch the output according to the existing settings until the changes are complete WARNING Fluid 1 Check the regulator and flow adjustment valve before introducing...

Отзывы: