15
FLOW & PRESSURE SENSOR
( INSTRUCTION MANUAL )
MFP01
How to use
–
Functions instructions
Function
code
Item
Default setting
Explanation
F-01
oUt1
OUT1 setting
oUt1
Select output 1 corresponding to
flow sensor or pressure sensor.
Set the flow rate or pressure
value to switch ON / OFF.
oUt1
OUT1 sensor correspondence
FLoy
FLoy
OUT1 output mode
KY5
oUt1
OUT1 output type
no
FL-1
OUT1 set value input
50 % of maximum measured flow rate
005 : 250 mL/min, 010 : 500 mL/min
050 : 2.50 L/min, 100 : 5.00 L/min
500 : 25.0 L/min, 101 : 50.0 L/min
201 : 100 L/min
FK-1
OUT1 set value input
60 % of maximum measured flow rate
005 : 300 mL/min, 010 : 600 mL/min
050 : 3.00 L/min, 100 : 6.00 L/min
500 : 30.0 L/min, 101 : 60.0 L/min
201 : 120 L/min
F-02
oUt2
OUT2 setting
oUt2
Select output 2 corresponding to
flow sensor or pressure sensor.
Set the flow rate or pressure
value to switch ON / OFF.
oUt2
OUT2 sensor correspondence
FLoy
FLoy
OUT2 output mode
KY5
oUt2
OUT2 output type
no
FL-2
OUT2 set value input
50 % of maximum measured flow rate
005 : 250 mL/min, 010 : 500 mL/min
050 : 2.50 L/min, 100 : 5.00 L/min
500 : 25.0 L/min, 101 : 50.0 L/min
201 : 100 L/min
FK-2
OUT2 set value input
60 % of maximum measured flow rate
005 : 300 mL/min, 010 : 600 mL/min
050 : 3.00 L/min, 100 : 6.00 L/min
500 : 30.0 L/min, 101 : 60.0 L/min
201 : 120 L/min
F-03
CLor
LCD display setting
CLor
Select back light color and
display mode.
d15p
LCD display corresponding to output
oUt1
d15p
LCD display color selection
5oG
F-04
rE5P
Response time selection
rE5P
Select the response time for
analog output.
Pressure sensor: 2.5 ms ~ 1500 ms
Flow sensor: 50 ms ~ 1500 ms
rE5P
Flow / Pressure sensor selection
FLoy
FLoy
Response time selection
800
(ms)
F-05
UPdR
Display refreshtime selection
UPdR
Display refresh cycle can be set
in 200 ms, 500 ms or 1000 ms.
UPdR
Flow / Pressure sensor selection
FLoy
UPdR
Display refresh time of flow sensor
selection
500
(ms)
F-06
Un1t
Unit selection
Un1t
Select the UNIT of pressure /
flow sensor.
FLoy
Flow unit selection
LPA
PrE5
Pressure unit selection
PR
Function setting mode