Enhancement Param.
P905
Transmit Pulse
Press
to supply repeated transmit pulses to the transducer and/or view the
transducer operating frequency (automatically altered by (P004) Transducer).
This feature may be used to monitor the transmit pulse with an oscilloscope
connected to the transducer terminals.
Values:
10.00 to 60.00
P906
Communications
Press
to test the SPL communications circuitry.
Note:
Before activating this feature connect terminal block contacts 27 to 29 and 28 to
30.
On successful test completion, "PASS" is displayed. If "FAIL" is displayed, repeat the
test. (The first test performed sets up the auto polarity function).
P907
Programmer Interface
Press
to activate the programmer interface (two way infrared communications)
test.
On successful test completion, "PASS" is displayed. Otherwise, "FAIL" is displayed.
P910
Relay
Access this parameter to display the current state of the specified relay.
Press
to alter the relay state (energized / de-energized) or enter the value
corresponding to the specific relay state desired.
Values:
0 = de-energized
1 = energized
P911
mA Output Value
Access this parameter to display the current value of the mA output.
Additionally, this feature may be used to enter a desired value. The mA output is
immediately forced to the value entered, regardless of any restrictions programmed.
Values:
0.000 to 25.00
Содержание AiRanger SPL PL-573
Страница 1: ...AIRANGER SPL Instruction Manual PL 573 March 2001 IRANGER SPL 33455730 Rev 1 2 ...
Страница 8: ...Page 8 AiRanger SPL PL 573 Specifications ...
Страница 24: ...Page 24 AiRanger SPL PL 573 Installation ...
Страница 86: ...Page 86 AiRanger SPL PL 573 Enhancement Param ...
Страница 102: ...Page 102 AiRanger SPL PL 573 Maintenance ...
Страница 108: ...Page 108 AiRanger SPL PL 573 Troubleshooting ...