With Quick Start parameter alteration complete, the SPL may be put into operation.
(If Application or Enhancement Parameters are altered, Operation is altered
accordingly from that indicated).
Display
In the RUN mode, the following values and indicators may be observed.
Note that many indicators are specific to certain operating conditions and therefore,
all indicators are not displayed at any given time.
Display Segment
Description
Transducer
the current display pertains to a transducer measurement.
Reading
displays the level, space, or distance (flashes error messages, if
any).
Percent
the Reading is in percent.
High Alarm
indicates level has risen above 80% (and not yet fallen below 75%).
Low Alarm
indicates level has fallen below 20% (and not yet risen above 25%).
Filling Indicator
indicates the vessel is filling.
Emptying Indicator
indicates the vessel is emptying.
Bar Graph
indicates the
absolute
(always a positive value) material level
from 0 to 100%.
Data Out
indicates the SPL is transmitting data to the Peripheral
Communications terminals.
Transducer Active
indicate the Point Number scanned (independent from the
Point Number display).
Auxiliary Reading
as selected by the keypad (terminal numbers if transducer or
TS-3 is wired wrong).
Relay Number
indicates the relays programmed for operation.
Relay Status
indicates the relay is de-energized (alarm is activated).
Normal Operation
indicates operating conditions are good and the Reading is
reliable.
Failsafe Operation
indicates operating conditions are poor and the Reading may
be incorrect.
normal
operation
failsafe
operation
units
transducer
reading
high alarm
indicator
filling/
emptying
indicator
bar
graph
low alarm
indicator
data out
indicator
transducer
active
auxiliary
reading
number
status
Содержание AiRanger SPL PL-573
Страница 1: ...AIRANGER SPL Instruction Manual PL 573 March 2001 IRANGER SPL 33455730 Rev 1 2 ...
Страница 8: ...Page 8 AiRanger SPL PL 573 Specifications ...
Страница 24: ...Page 24 AiRanger SPL PL 573 Installation ...
Страница 86: ...Page 86 AiRanger SPL PL 573 Enhancement Param ...
Страница 102: ...Page 102 AiRanger SPL PL 573 Maintenance ...
Страница 108: ...Page 108 AiRanger SPL PL 573 Troubleshooting ...