Enhancement Param.
P704
Rate Filter
Use this feature to avoid Rate Value (P707) fluctuations due to a "splashing" material
surface.
This value is automatically altered when Measurement Response (P003) is altered.
See Technical Reference / Measurement Response.
This value automatically alters the Rate Update Time (P705) and / or Rate Update
Distance(P706). Alternatively, these parameter values may be altered independently.
Enter the time period/distance the Rate Value is averaged before display update.
Values:
0 = rate display not required
1 = continuously averaged and updated
2 = 1 minute or 50 mm (2 in)
3 = 5 minutes or 100 mm (3.9 in)
4 = 10 minutes or 300 mm (11.8 in)
5 = 10 minutes or 1000 mm (39.4 in)
P705
Rate Update Time
Enter the time period (in seconds) over which the material level rate of change is
averaged before Rate Value update.
Values:
0.000 to 9999
P706
Rate Update Distance
Enter the material level change (in metres) to initiate a Rate Value update.
Values:
0.000 to 9999
P707 (V)
Rate Value
View the rate of material level change (in Units (P005) or % of Span (P007) per
minute).
Note:
A negative rate indicates the vessel is emptying.
This is the value displayed when
is pressed in the RUN mode.
Values:
-999 to 999
Содержание AiRanger SPL PL-573
Страница 1: ...AIRANGER SPL Instruction Manual PL 573 March 2001 IRANGER SPL 33455730 Rev 1 2 ...
Страница 8: ...Page 8 AiRanger SPL PL 573 Specifications ...
Страница 24: ...Page 24 AiRanger SPL PL 573 Installation ...
Страница 86: ...Page 86 AiRanger SPL PL 573 Enhancement Param ...
Страница 102: ...Page 102 AiRanger SPL PL 573 Maintenance ...
Страница 108: ...Page 108 AiRanger SPL PL 573 Troubleshooting ...