Enhancement Param.
Enter the level value in Units (P005) or percent of Span (P007) as referenced to
Empty (P006).
(Ensure the % Symbol is displayed before attempting to enter a value in percent, see
Programming / Keypad).
P334 (G)
Auto Record A Setpoint
Enter the critical level which, in conjunction with Auto Record B Setpoint, defines the
boundaries for Auto Profile Records to be stored.
Values:
-999 to 9999
P335 (G)
Auto Record B Setpoint
Enter the critical level which, in conjunction with Auto Record A Setpoint, defines the
boundaries for Auto Profile Records to be stored.
Values:
-999 to 9999
P336 (G)
Auto Record Filling/Emptying
Use this feature to restrict Auto Profile Records from being saved unless the level is
rising, falling or either.
If the level changes at a rate in excess of the corresponding Filling/ Emptying
Indicator (P702 / P703) values, the Echo Profile is saved subject to this and other
Auto Profile Record restrictions).
Values:
0 = Auto Profile Record on filling or emptying (preset).
1 = Auto Profile Record on filling only.
2 = Auto Profile Record on emptying only.
P337 (G)
Auto Record LOE Time
Use this feature to restrict Auto Profile Records from being saved unless an extended
loss of echo (LOE) condition occurs.
If the LOE condition exceeds the period entered (in seconds) the Echo Profile is
saved subject to this and other Auto Profile Record restrictions.
When set for “0” (preset), LOE is not required for an Auto Profile Record to be saved.
Values:
0.0 to 9999
Содержание AiRanger SPL PL-573
Страница 1: ...AIRANGER SPL Instruction Manual PL 573 March 2001 IRANGER SPL 33455730 Rev 1 2 ...
Страница 8: ...Page 8 AiRanger SPL PL 573 Specifications ...
Страница 24: ...Page 24 AiRanger SPL PL 573 Installation ...
Страница 86: ...Page 86 AiRanger SPL PL 573 Enhancement Param ...
Страница 102: ...Page 102 AiRanger SPL PL 573 Maintenance ...
Страница 108: ...Page 108 AiRanger SPL PL 573 Troubleshooting ...