Communication, P751 - P761
These parameters are specific to the use of the communication parameters.
Refer also to Appendices\Communication.
P751
baud rate
Sets the baud rate for the proprietary bi-polar current loop. This baud
rate is not applicable to communication via Milltronics Comverter.
entry: 300, 1200, 2400, 4800 or 9600 baud
4800 baud is required for Dolphin communications over the
bi-polar current loop.
P760
communication mode
Selects the communication mode.
» bi-polar current loop:
interface with the host device (PLC or computer)
is made through the Milltronics BIC-2 or CVCC.
Refer to Operation\Communication.
» infrared link:
communication is made using the
Milltronics ComVerter.
» maintenance:
communication is made via the bi-polar current
loop for run mode operations and infrared link
for program mode operations
entry: 1 = bipolar current loop
2 = infrared link
3 = maintenance
P761
identification number
Sets the identification number for the unit.
enter the desired identification number, range 0 - 15
End of communication parameters.