Relay/Alarm Function, P100 - P117
These parameter are specific to the use of the relay/alarm function.
Refer to Operation\Relay Output.
P100
relay set up
Sets the alarm mode for the relay.
entry: 0 = off
1 = rate
2 = auto zero
3 = belt speed
4 = belt load
5 = error
P101
high alarm
Sets the high alarm setpoint for relay functions P100 = 1, 3 or 4.
enter the value in % of full scale
P102
low alarm
Sets the low alarm setpoint for relay functions P100 = 1, 3 or 4.
enter the value in % of full scale
P117
alarm dead band
Sets the dead band to prevent relay chatter due to fluctuations
at the high or low setpoint.
enter the value in % of full scale
End of relay/alarm parameters.