OM-253 918 Page 20
956142881_5-A
Tools Needed:
4-11. Connecting 230 VAC Single Phase Input Power
!
Installation must meet all National
and Local Codes
−
have only quali-
fied persons make this installation.
!
Disconnect and lockout/tagout in-
put power before connecting input
conductors from unit.
!
Always connect green or green/
yellow conductor to supply
grounding terminal first, and never
to a line terminal.
See rating label on unit and check input
voltage available at site.
1
Input Power Cord
2
Disconnect Device (switch shown in
the OFF position)
3
Disconnect Device Grounding
Terminal
4
Disconnect Device Line Terminals
5
Black And White Input Conductor
(L1 And L2)
6
Green Or Green/Yellow Grounding
Conductor
Connect green or green/yellow grounding
conductor to disconnect device grounding
terminal first.
Connect input conductors L1 and L2 to
disconnect device line terminals.
7
Over-Current Protection
Select type and size of over-current
protection using Section 4-10 (fused dis-
connect switch shown).
Close and secure door on disconnect
device. Remove lockout/tagout device,
and place switch in the On position.
2
1
L1
L2
1
6
5
3
4
7