12.0 conventional
flue installation
The Strata 1 boiler has an excess pressure combustion system, which coupled with the very low flue
gas temperatures produced allows the appliance to exhausted over considerable distances using 80mm
Polypropylene PPS flue pipe and fittings. Suitable flue pipe and fittings are available from MHS Boilers Ltd
and are listed below.
The flue should be installed to have at least a 3° fall to the boiler to allow any condense formed in the
flue to run back to the boiler.
The flue system used must be gas and water tight and must be adequately supported over it’s entire
length. Support at 1 metre intervals. It is not necessary to install a terminal to the flue system, however, a
mesh guard should be included to prevent blockage or entry of foreign material. Straight lengths may be
cut to size with any surplus cut from the plain end. Tube ends should be cut square and de-burred.
Care should be taken when selecting a position for a low level discharge or discharge adjacent to
windows etc as the flue terminal will plume heavily and the white water vapour discharge may cause a
visual nuisance.
Flue components available from MHS Boilers Ltd
80 mm PPS Flue Tube x 1000 mm long
(effective length 945 mm)
80 mm PPS Flue Bend x 93°
80 mm PPS Flue Bend x 45°
80 mm Wall Fixing Bracket - Aluminium
80 mm Bird Mesh Cap - Plated Steel
The above flue components
are light grey self
coloured
Polypropylene moulded com-
ponents with push together
spigot and socket joints
with integral seal ring located in
the socket.
If fire stop seals are required
to be installed where PPS plastic
flue components pass through
walls, floors or ceilings then
suitable fire stop seals are
available from:-
Nullifire Ltd
Torrington Avenue
Coventry CV4 9TJ
Tel 02476 855000
Fax 02476 469547
Dufaylite
Developments Ltd
Cromwell Road, St Neots
Huntingdon PE19 1QW
Tel 01480 215000
Fax 01480 405526
Quelfire
PO Box 35, Altrincham
Cheshire WA14 5QA
Tel 0161 928 7308
1000 mm
Effective Length 945mm
137
125
ø80
ø80
50
65
75
ø80
50
100
150
50
80 ø PPS
Flue Tube
x 1000
long
80 ø
PPS Flue
Bend
x 93º
80 ø
PPS Flue
Bend
x 45º
80 ø Wall
Fixing Bracket
ø5 Woodscrew
fitting
100 mm PPS Flue Tube x 1000 Long (Effective Length 945 mm)
100 mm PPS Flue Bend x 93°
100 mm PPS Flue Bend x 45°
100 mm Wall Fixing Bracket
100 mm Bird Mesh Cap - Plated Steel
80 x 100 mm Increaser
80 ø PPS flue components
100 ID
56
50
150
80 x 100 PPS
Increaser
End Slip
80