Temperature:
choose the temperature unit (°C or °F) from the selection box.
High threshold:
if this value is exceeded, a
notification
is sent if this is validated. Default value is 40 °C / 104
°F.
Low threshold:
if this value is exceeded, a
notification
is sent if this is validated. Default value is 5 °C / 41 °F.
Hysteresis
must be set to prevent multiple notifications if temperature fluctuates around a threshold.
Default value is 2 °C / 3.6 °F. (Advanced parameters)
The high alarm cannot be reactivated while temperature remains above the
High threshold – Hysteresis
value.
The low alarm cannot be reactivated while temperature remains below
Low thr hysteresis
value.
Humidity
High threshold:
if this value is exceeded, a
notification
is sent if enabled. Default value is 90%.
Low threshold:
if this value is exceeded, a
notification
is sent if enabled. Default value is 5%.
Hysteresis
must be set to prevent multiple notifications if humidity fluctuates around a threshold.
Default value is 5%. (Advanced parameters)
The high alarm cannot be reactivated while humidity remains above the
High threshold – Hysteresis
value.
The low alarm cannot be reactivated while humidity remains below
Low thr hysteresis
value.
Input No 1
and
Input No 2:
enter an identifier corresponding to the acquired contact (e.g.: rack door, air
conditioning, generator unit, etc.). Max. length is 28 characters.
If contact closed
and
if contact open:
are the names associated to the two contact positions. (e.g.: "open"
and "closed" for a door, "On" and "Off" for a generator).
Each status change triggers a
notification
if enabled.
Notification
includes: Log, Notification by e-mail and generation of SNMP Trap. The list of messages is given
in the
appendix
.
System shutdown
can be triggered for each notification if this option is enabled. If notification is disabled, the
Shutdown option cannot be used. (Advanced parameters)
Security:
the administrator has to click on Save and enter his login/password to save any modifications.