“Immediate off”:
a sequence to switch off output power is launched immediately. The symbol representing the
output flashes, indicating that the sequence is in progress. The systems supplied are shut down correctly while
the shutdown sequence is running, then the output is cut.
“Immediate Toggle”:
A sequence to switch off then restore output power is launched immediately. The symbol
representing the output flashes, indicating that the shutdown sequence is in progress. The powered systems
are shut down correctly during the shutdown sequence, then the output is switched off.
Finally, the restart sequence is launched at the end of the time delay specified in the
“Toggle duration”
parameter. The output status is updated.
Immediate On:
a sequence to switch on output power is launched immediately. The output is re-powered and
the systems supplied start up again correctly.
Delayed Off:
this is the same switch off sequence as for the “
Immediate off
” command, but postponed by the
number of seconds programmed in the “
Off Delay
” parameter.
Delayed Toggle:
this is the same switch off then on sequence as for the “
Immediate Toggle
” command, but
postponed by the number of seconds programmed in the “
Off Delay
” parameter.
Delayed Off:
this is the same switch on sequence as for the “
Immediate On
” command, but postponed by the
number of seconds programmed in the “
On Delay
” parameter.
The
Save
button saves the
Off Delay
,
Toggle duration
and
On Delay
parameters on the card .
Security:
The administrator must click on
Save
and enter his login / password to save modifications or run
commands. The login and password by default are
: MGEUPS.