Name and status of each contact can be configured
◗
Recording of events and measurements in the card log
◗
Possibility of shutting down the installation safely if one of the thresholds is exceeded or if a dry contact
closes
◗
Connection to the Network Management Card by CAT5 straight RJ45 network cables (maximum
card/sensor distance: 20m)
3.6.2 Environment
status
For both measurements, a graduated gauge proposes the following functions:
The cursor indicates the current value.
Two red zones to the left and right represent the high and low thresholds that can be set on the
Environment
Settings
page.
When the measured value enters one of these zones, a alarm can be notified (see
Notification
parameter in
the
Environment Settings
page).
Time-stamped minimum and maximum temperatures show the extreme values recorded since the last
Reset
Min/Max
, a thin dotted line shows their positions on the gauge.
Min and Max can be forced at any time to the current value by clicking on the
Reset Min/Max
button.
Calibrate:
the sensor is calibrated in the factory, but the user can apply an offset to adjust the measurement.