5
3
480B/SFL2Dx SHEATH FAULT LOCATOR QUICK START
FOR THE EXPERIENCED USER
1
Check batteries prior to departing for the field
Check the batteries in the Transmitter, Receiver, and A-Frame.
Replace/recharge if necessary. Turn the instruments off.
2
Ensure all conductors are de-energized
3 Lift grounds
Lift Grounds (of all conductors in the circuit) at both ends of the faulted cable
section.
WARNING
When the Transmitter is set to “FAULT & LINE LOCATE”, the external FAULT
OUTPUT jacks produce High Voltage.
Do not touch these jacks, electrical shock
will result!
4
Attach transmitter to conductor – Check Fault Resistance
1 Turn Transmitter “OFF.”
2 Plug Black and Red leads into the Transmitter.
3 Stretch Black-lead 180 degrees away from conductor.
4 Push grounding rod into earth and clamp black lead to grounding rod.
Establish the best ground possible
. See figure 3-2
5 Clamp Red lead to target conductor sheath.
See Figure 3-3
6 Turn transmitter power knob to “Fault & Line Locate” position.
Check fault resistance scale:
See Figure 3-1
0-100k ohms – Severe Fault
100k – 500k ohms – Medium Fault
1 Megohm and above – Light Faults
Note:
Read the number below the solid
bars to check the quality of the targeted
cable. The fault resistance on
Figure 3-1
is 20K ohms (Severe Fault).
Figure 3-1: Fault Resistance Scale