32
7.5 Synchronize the A-Frame Receiver
By synchronizing, the A-Frame memorizes the phase of the Transmitter signal. This
allows it to recognize the reverse phase signal coming from the fault and direct you to
it.
Note
:
Resynchronize the Receiver every 45 minutes to maintain calibration. You may do
this near the ground rod or near a fault. At the ground rod, the black A-Frame spike
must be nearest the ground rod. At a fault, the white A-Frame spike must be nearest
the fault.
1
Hold the A-Frame so the black spike is closest to the ground rod.
2
Push the A-Frame spikes into the ground.
3
Switch the Receiver “ON”. Wait until the arrow flashes.
4
If the arrow points away from the ground spike, there is a fault.
5
If the arrow points towards the ground spike, there is not fault, or grounds and
connections need to be rechecked. See
Figure 7-1.
Figure 7-1: Synchronizing The A-frame