36
8.1.2 Triangulation Method.
As shown in
Figure 8-2
, (the point where the signal strength is a minimum) if the A-Frame is
positioned exactly on an equipotential circle, a perpendicular line from the center of the A-
Frame will pass through the fault. The intersection of any two such perpendicular lines
defines the fault location.
Paved Surface
Cable
Fault
Figure 8-2: Triangulation Method
To find an equipotential circle (see
Figure 8-3
) insert the A-Frame into the ground and pivot
around one spike. Rotate the A-Frame back and forth until the exact point is found where the
flashing arrows change direction. The A-Frame is now on an equipotential circle and is
perpendicular to the fault. By marking this line and repeating the process with the A-Frame
at another nearby location, the two lines will intersect or cross at the fault.
Figure 8-3: Locating an Equipotential Circle