MI 3321 MultiservicerXA
Machine testing operating mode
133
The displayed contact voltage is proportional to the rated nominal residual current of the
RCD and multiplied by appropriate factor. The 1.05 factor is applied to avoid negative
tolerance of result. An additional factor depends on RCD type and type of test current.
See table below for detailed contact voltage calculation.
RCD type
Contact voltage Uc
proportional to
Rated I
N
AC
G
1.05
I
N
any
all instrument
versions
AC
S
2
1.05
I
N
A
G
1.4
1.05
I
N
30 mA
A
S
2
1.4
1.05
I
N
A
G
2
1.05
I
N
< 30 mA
A
S
2
2
1.05
I
N
B
G
2
1.05
I
N
any
instrument HW
version 3.0 and
higher
B
S
2
2
1.05
I
N
Relationship between Uc and I
N
Loop resistance result is indicative and calculated from Uc result (without additional
proportional factors) according to following equation:
N
C
L
I
U
R
Example of contact voltage measurement results
Displayed results:
Main result ............. Contact voltage.
Rl ........................... Fault loop resistance.
Ul-pe ...................... Voltage UL-PE
Un-pe ..................... Voltage UN-PE