9.2
Electrical Specifications
Unit / Interface
Feature
Value
Display
128 x 64 dot graphic LCD
Keypad
3 short-travel keys
Analog Input 1/2
Voltage range:
0 to 10 V
Reference potential:
ground
Input resistance
approx. 50 k
Ω
Resolution
24 bit
Current Loop
Signal Current:
0/4 to 20 mA
Reference potential:
fully floating, max.
±
500 V to ground
Burden:
max. 800
Ω
Resolution:
16 bit
Analog Output 1/2
Voltage range:
0 to 10 V
Reference potential:
ground
Load resistance:
min. 10 k
Ω
Resolution:
16 bit
Relay 1/2/3
Maximum Voltage:
30 V
Switching current:
0.5 A (max.)
Switching capacity:
10 W (max.)
Reference potential:
fully floating,
max.
±
500 V to ground
Power Supply
Voltage range:
18 - 26 V DC
Max. current:
1 A
Typical current draw:
500 mA
Safeguard:
PELV (Protective Extra Low Voltage)
Digital Interface
Type:
RS-232
Baud rate:
19.2 kbaud
Data:
8 bit
Parity:
None
Stop:
1
Flow control
None
Reference potential:
ground
Table 9.2: Electrical Specifications