STOP SWITCH (OPTIONAL) MODEL: 600084
A stop switch to stop the movement of the gate in any direction can be connected to this output.
Also see STOP/8.2kOHM under “Jumper Settings”.
FLASHING LAMP (OPTIONAL) MODEL: FLA24-2
A flashing lamp can be connected to the control board. It warns when the gate is being moved. The flashing light should be fitted as high as
possible and in good clear view. The control board emits a constant signal that the lamp converts to a flashing signal.
Cable cross-section: 0.5 mm
2
or more.
Voltage: 24 V DC
KEY SWITCH (OPTIONAL) MODEL: 100010, 100027, 100034, 100041
The system can be operated by key switch (connectors: key symbol and COM). Also see OPEN/PED under “Jumper Settings”.
BACKUP BATTERY (OPTIONAL) MODEL: CM475 (24V/DC)
The terminals serve to reload an externally installed storage battery.
The integrated recharger is loaded and in case of power failure the battery provides power. A new fully charged storage battery may provide
power for more than 24 hours. Storage batteries are subject to deterioration and lose capacity. Due to extensive use they lose capacity even
faster. Replace storage batteries after approx. 2-3 years. CM475 is not for outside use and requires a suitable enclosure.
SAFETY EDGE (OPTIONAL) MODEL: 600046, 600053, 600077, 600060
A safety edge working according to the 8.2 kilo ohm principle can be connected to the control board, i.e. a 8.2 kilo ohm test resistor is attached
to the end of the safety edge. It ensures that the electric circuit is monitored permanently. The control board is supplied with an 8.2 kilo ohm
resistor installed. Several safety edges are connected in series. Cable cross-section: 0.5 mm
2
or more.
Also see STOP/8.2kOHM under “Jumper Settings”.
ANTENNA (OPTIONAL) MODEL: ANT4X-1LM
The control board is supplied with a wire antenna as standard. An external antenna (accessory) can be connected to terminals as shown.
A larger range (radio) can thus be achieved. For best range results mount antenna as high as possible.
PHOTOCELLS (INCLUDED) MODEL: 772ANZ
The photocells are for safeguarding the gate and must be used.
The fitting location depends on the gate’s design. EN12453
specifies that a pair of photocells must be installed at a height of
200 mm and activated to “Close”. The photocells consist of a
transmitter and a receiver and must be opposite each other. The
photocell is mounted on the wall using small screws and wall plugs.
To enable the “Automatic Closing” function, the Chamberlain failsafe
photocell must be installed.
Programming of IR sensors:
- connect IR sensors
- program the travel of the gate
- special feature: Fast closing gate
(see “Description of the Push Buttons P1, P2 & P3”)
Deletion of IR sensors:
Disconnecting already connected IR sensors will cause the control
board to block the functionality of the terminals it was connected to.
To delete IR sensors correctly:
- disconnect IR sensors
- cut control board from current shortly
- program the travel of the gate.
Diagnosis of the photocell
LED constant = OK
LED flashes = photocell disables control board
LED off = no current, incorrect connection or polarity
Diagnosis on the control board
LED constant = OK
LED off = OK no photocell connected
LED flashes = photocell disables control board
Connection between 1 & COM:
Active when gate is closing (reverses gate to open)
Connection between 2 & COM:
adjustable:
Jumper “PHO 2 MODE” unplugged >> active when gate is closing
Jumper “PHO 2 MODE” plugged >> active when gate is opening
230V~
+/- 10%
50Hz
Model
CM475
(enclosure
required)
Ω
8.2
+
+
+
+
+ +
opening beam
closing beam
closing beam
closing beam
PHO1
PHO2
Radio
433MHz
Jumper OFF
Jumper ON
BL
BL
Grey