38
WARNING
DO NOT PROCEED WITH OPERATION OF THIS FIREPLACE
UNLESS BURNER "CYCLES" ON/OFF WITHOUT DELAYS!
CHECKING FOR NORMAL BURNER (S) IGNITION CHARACTERISTICS
Once the conversion to LPG and all the above steps have been completed, light the main burners.
Press "ON" button on Remote Transmitter. Pilot should ignite after gas line is purged of air and Main burner should now
light and flame should not "lift" off burner. If there is any delay in ignition or if flame is "lifting off" burner, turn off burner
and carefully check for proper installation of media, vent system and proper pilot flame impingement on burner and ther-
mopile. Logs or coals must not block pilot flame or main burner flame. Vent system must be leak proof.
ATTACHING LPG CONVERSION LABELS AND HIGH ALTITUDE DERATION LABEL
Two printed informational labels are included with the LPG Conversion Kit. Attach these two labels to the rear surface of
this insert adjacent to the Serial Number Plate. If you are derating this appliance at a high altitude, also attach the High
Altitude Deration Label, supplied in the Owner’s Manual Packet, to this same surface adjacent to other labels.
Prior to attaching the labels, fill in all the information that is requested in these labels.
For installations from 610-1370 meters (2000-4500 ft.) the orifice sizes (DMS) for natural and propane gas are _#42_ and
_#53”_, respectively. See data plate for additional information. For high altitude installations consult the local gas distrib-
utor or the authority having jurisdiction for proper rating methods. If the installer must convert the unit to adjust for varying
altitudes, the information sticker must be filled out by the installer and adhered to the appliance at the time of conversion."
«Cet appareil est equipé pour des altitudes compries entre 0 et 2000 pieds (0-610 m) seulement»
This appliance has been converted for use at an altitude of ______________
Orifice size _______________
Manifold Pressure ________________
Input (Btu/h)_______________
Fuel Type _______________________
Date of conversion _________
Converted by _____________________
«Cet appreeil a été converti au ____
Injecteur ________
Pression à la tubulure d'alimentation _____________
Déoit calorifique ______________
GAS LEAK TEST REQUIREMENT: It is the responsibility of the installer/service person to assure
that each and every gas connection and supply tubing that are a part of this fireplace are leak proof.
The qualified/ certified individual connecting the gas supply line, performing pressure tests or per-
forming any service to this fireplace is required to perform a THOROUGH LEAK TEST on ALL gas fit-
tings that are a part of this appliance or the gas supply line connection using soap-water solution or a
calibrated combustible gas detector. Failure to perform this leak test may lead to a house fire and/or
an explosion. Mendota is not responsible for any damages due to an Installer’s failure to conduct a
leak test and verify that all connections and supply lines are leak proof.
WARNING: Do not operate appliances with glass front removed, cracked, or broken. Replacement of glass
should be done a licensed or qualified service person.
Note: Consult the local or national installation code(s) to assure that adequate combustion and ventilation air is
available.
WARNING: It is of the utmost importance that the correct burner orifices be installed for the burner.