FV36 DÉCOR Master Venting Chart
Note: This chart is applicable to both natural gas and LP installations.
❑
9” minimum vertical pipe run required to be connected directly to this fireplace’s flue
starter
collar.
❑
Maximum horizontal run allowed with the minimum 9” vertical run is 12”.
❑
Maximum vertical run allowed is 40’.
❑
Maximum vent system length allowed is 44’.
❑
32’ maximum horizontal run allowed with a minimum 4 to 12’ starter section. Three 90
°
elbows
may be installed anywhere within the 32’ horizontal run. If the starter vertical section is less
than 4’, use the chart and reduce 3’ for every 90
°
elbow installed after the first 90
°
elbow.
❑
For all vertical terminations, four 90
°
elbows allowed. However, the fourth 90
°
elbow must
point vertically and directly to the vent termination cap.
High Altitude Installation Information
Prior to installing at altitudes higher than 7500, please contact the Mendota technical service department for specific venting
requirements and venting restrictions.
V min
H max
9
”
1
2”
12
”
3
’ 5”
2
’
1
2’ 11”
3’
2
2’ 6”
4’ –
12’
32’
12’
–
40’
Varies
13'-9"
18'-3"
22'-10"
27'-5"
32'-0"
3'-5"
12'-11"
22'-6"
32'-0"
9"
1'-0"
2'-0"
3'-0"
4'-0"
12'-0"
16'-0"
20'-0"
24'-0"
28'-0"
32'-0"
36'-0"
40'-0"
1'-0"
8'-0"
4'-0"
8'-0"
12'-0"
16'-0"
20'-0"
24'-0"
28'-0"
4'-7"
9'-2"
Figure 3-49 MASTER VENT CHART
Содержание AA-11-04109
Страница 2: ...85 03 01154 FV36 D COR...
Страница 16: ...85 03 01154 FV36 D COR Page 16 Figure 3 11 Figure 3 10...
Страница 24: ...85 03 01154 FV36 D COR Page 24 Clearance from Appliance Side Walls Figure 3 17 CLEARANCE TO BODY...
Страница 87: ...85 03 01154 FV36 D COR Page 87 Gas Train Assembly Parts Figure 5 5 Gas Train Assembly Parts...
Страница 88: ...85 03 01154 FV36 D COR Page 88 Burner Figure 5 6 Burner...
Страница 95: ......
Страница 96: ...Johnson Gas Appliance Company 520 E Avenue NW Cedar Rapids Iowa 52405 Mendota Warranty Registration...