Burner Ignition Characteristics
Note: Connect gas supply and verify that the minimum inlet and outlet pressures are conforming.
Once the conversion to LPG and all the above steps have been completed, light the main burner.
Use remote transmitter to turn on pilot light and burner. Main burner should now light IMMEDIATELY and flame should not
"lift" off burner. If there is any delay in ignition or if flame is "lifting off" burner, turn off burner and carefully check for proper
installation of logs/coals, vent system and proper pilot flame impingement on burner. Logs or coals must not block pilot flame
or main burner flame. Vent system must be leak proof.
WARNING: Do not proceed with operation of this fireplace unless burner "cycles" on/off without delays!
Pilot Flame and Burner Relationship Verification
Prior to completing the LPG conversion process, the qualified service technician must light the pilot light and verify the
relationship between the pilot light flames and the main burner. The pilot light flames directed towards the propagation ports
on the rear and front burner must overlap the propagation ports on the burner.
The pilot light flames must be a minimum of 1” long and must overlap the propagation ports on the
burner.
Verify that the burner tubes ignite quickly and the burner flames propagate smoothly along the entire
length of the burner.
Figure 3-48 Pilot Flames
1" MIN.
1" MIN.
Содержание AA-11-04109
Страница 2: ...85 03 01154 FV36 D COR...
Страница 16: ...85 03 01154 FV36 D COR Page 16 Figure 3 11 Figure 3 10...
Страница 24: ...85 03 01154 FV36 D COR Page 24 Clearance from Appliance Side Walls Figure 3 17 CLEARANCE TO BODY...
Страница 87: ...85 03 01154 FV36 D COR Page 87 Gas Train Assembly Parts Figure 5 5 Gas Train Assembly Parts...
Страница 88: ...85 03 01154 FV36 D COR Page 88 Burner Figure 5 6 Burner...
Страница 95: ......
Страница 96: ...Johnson Gas Appliance Company 520 E Avenue NW Cedar Rapids Iowa 52405 Mendota Warranty Registration...