8.1 Example 1
3-phase circuit breaker with
two interrupters per phase and
separate operating mechanism
with DualGround
Test quantities
Main contact timing measured by the DCM and Timing M/R
modules
Auxiliary contact timing (one a & one b contact) measured
by the Control module
Coil current & voltage measured by the Control module
Transducer in use
N/A
Others
No resistor contacts
Fig. 8.1 Uppkoppling (per fas)
.
Necessary settings in Breaker View
Breaker View
Number of phases
3
Operating mechanism
Separate
Number of interrupters per phase
2
Resistor contacts
None
Number of a-contacts per phase
1
Number of b-contacts per phase
1
Breaker View \
Pulse & Delay Times
These settings are depending on the circuit breaker
type. Please refer to the breaker manufacturers data.
Breaker View \
Measurement Preferences
Coil current
On
Control voltage
On
Sense voltage
On
Breaker View \ Measurement Preferences \
Settings
DCM
On
Breaker View \ Measurement Preferences \
Measurement Time & Sample Interval
The default settings should be sufficient in most of
the cases.
82
TM1800
ZP-CG01E
CG0757JE
8 APPLICATION EXAMPLES
8
A
pplication examples
Содержание TM1800
Страница 2: ......
Страница 7: ...CG0757JE ZP CG01E TM1800 7...
Страница 17: ...CG0757JE ZP CG01E TM1800 17 3 System overview...
Страница 25: ...CG0757JE ZP CG01E TM1800 25 3 System overview Keyboard in position 3...
Страница 71: ...CG0757JE ZP CG01E TM1800 71 7 Perform testing...
Страница 97: ...CG0757JE ZP CG01E TM1800 97 12 Quick Guide...
Страница 103: ......