4 MODULES
Number of modules needed
1 module to measure circuit breakers with up to 2 breaks
per phase
2 module support circuit breakers with up to 4 breaks per
phase
3 module support circuit breakers with up to 6 breaks per
phase
4.3 Timing M/R module
The Timing M/R module measures timing on Main
and Resistive (parallel) contacts. The module measures
up to six breaks with both main and resistive contact,
giving in total 12 measuring channels. The TM1800
system can be equipped with multiple Timing M/R
modules that enable any type of test setup to be per-
formed. All three connectors (phases) are galvanically
isolated and have built-in voltage source.
For specifications, see “Timing M/R Module” in chap-
ter 9 Specifications.
Terminal configuration
The module is equipped with three XLR female con-
nectors on the front grouped in phase sections named
A, B and C. Each connector has three pins for connec-
tion to two breaks.
1
First break point
2
Second break point
0
Common point for both breaks
Number of modules needed
1 module to measure circuit breakers with up to 2 breaks
per phase
2 modules supports circuit breakers with up to 4 breaks per
phase
Up to 8 modules can be mounted in the TM1800
Содержание TM1800
Страница 2: ......
Страница 7: ...CG0757JE ZP CG01E TM1800 7...
Страница 17: ...CG0757JE ZP CG01E TM1800 17 3 System overview...
Страница 25: ...CG0757JE ZP CG01E TM1800 25 3 System overview Keyboard in position 3...
Страница 71: ...CG0757JE ZP CG01E TM1800 71 7 Perform testing...
Страница 97: ...CG0757JE ZP CG01E TM1800 97 12 Quick Guide...
Страница 103: ......