7 PERFORM TESTING
7.5 Define a new circuit
breaker
1]
In Breaker list press the button “DEFINE
NEW BREAKER FROM TEMPLATE”. You have
to be at the top position, Circuit Breaker(s),
on the breaker list to see the button for
defining a new breaker.
2]
Select the MAX CONFIG TEMPLATE.
3]
Press the “EDIT BREAKER ID” button and
name the breaker.
4]
Press “BACK”
5]
Press “OK”
6]
Go to Breaker View.
7]
Set up your breaker settings. Refer to chap-
ter 6.5 for details.
Note
When you change settings in Breaker View
the breaker you have marked in Breaker List
will be changed.
8]
Go back to Breaker List.
9]
Press “Begin New Test” button.
10]
Give the test a identification (Test ID).
Choose type of test.
11]
Choose the operation sequence on the con-
trol panel.
12]
Turn Operating/Measure knob on the con-
trol panel.
13]
Now the system asks you to check the con-
nections and will automatically change to
Analyzer View.
14]
Follow the connection instructions.
15]
When done, turn the Operating/Measure
knob once again and the sequence will be
performed.
16]
Results can be checked on screen. Continue
with the remaining sequences.
7.6 Using circuit breaker
created in CABA Win
Breakers created in CABA contain less information than
breakers created in TM1800. Therefore, the missing
information has to be added when importing a CABA
breaker to the TM1800 unit. This addition of informa-
tion is done only when it is required, i.e. the first time a
breaker is imported to TM1800.
The added parameters will initially get default values
according to below. After completed import the user
has to go through the values under the Breaker View
tab. The user can change some of the values, see table
next page.
Note
If a breaker that has been located in TM1800 is
exported to an old version of CABA there is a
risk that some information get lost. In this case
the user will be notified that default values are
added and that he has to check all the settings
again
When a CABA breaker is imported to TM1800
the attached test plan is changed to a non-
edible type, which means that it can neither
be altered in CABA nor in TM1800 regarding
number of contacts etc. The reason behind this
is that changes might destroy the possibility to
compare old test results with new. However,
still speed calculation points can be edited in
CABA.
Содержание TM1800
Страница 2: ......
Страница 7: ...CG0757JE ZP CG01E TM1800 7...
Страница 17: ...CG0757JE ZP CG01E TM1800 17 3 System overview...
Страница 25: ...CG0757JE ZP CG01E TM1800 25 3 System overview Keyboard in position 3...
Страница 71: ...CG0757JE ZP CG01E TM1800 71 7 Perform testing...
Страница 97: ...CG0757JE ZP CG01E TM1800 97 12 Quick Guide...
Страница 103: ......