7 PERFORM TESTING
Dynamic Resistance Measurements
(DRM)
The DRM test method is very suitable for diagnostic
testing. Tests are conducted by injecting high DC
current, approximately 250 A or higher, through the
breaker and measuring the voltage drop and current
while the breaker is operated, not to be confused
with static resistance measurement (microohm meas-
urement), which measures contact resistance when a
breaker is closed.
The breaker analyzer then calculates and plots resist-
ance as a function of time.
DRM has a number of applications. On circuit break-
ers with an arching contact design (mainly SF6 types)
DRM can be used to measure the arcing contact wear.
When contact movement is recorded simultaneously,
you can read the resistance at each point of contact.
Since there are a significant difference in resistance
between the main- and arching contacts the resist-
ance graph and the motion graph will indicate the
length of the arching contact. In some cases, circuit
breaker manufacturers can supply reference curves for
the type of contact in question.
Other applications e.g. timing measurements can with
DRM be performed on circuit breakers grounded on
both sides. Either the circuit breaker has to be ground-
ed during test due to safety regulations or the circuit
breaker design does not allow removing one ground.
If a sufficiently high current is used (about 250 A or
higher), there will be a noticeable step in the voltage
change when the breaker contact closes or opens in
spite of the parallel ground connections. Similarly,
DRM can be used when a breaker has parallel main
contacts.
DRM example
Содержание TM1800
Страница 2: ......
Страница 7: ...CG0757JE ZP CG01E TM1800 7...
Страница 17: ...CG0757JE ZP CG01E TM1800 17 3 System overview...
Страница 25: ...CG0757JE ZP CG01E TM1800 25 3 System overview Keyboard in position 3...
Страница 71: ...CG0757JE ZP CG01E TM1800 71 7 Perform testing...
Страница 97: ...CG0757JE ZP CG01E TM1800 97 12 Quick Guide...
Страница 103: ......