6 HOW TO INSTALL INGVAR
Calculate the impedance
Number
of cables
Total cross section
area
Impedance, cables twisted
1)
(mΩ)
Max. current in
20 sec.
Max. continuous
current
Weight (total set)
1 pair
120 mm
2
(1 x 120)
(L x 0.43) + 0.1
1 600 A
350 A
(L x 2.7) + 1.9 kg
2 pairs
240 mm
2
(2 x 120)
(L x 0.22) + 0.1
3 200 A
700 A
(L x 5.4) + 1.9 kg
3 pairs
360 mm
2
(3 x 120)
(L x 0.14) + 0.1
4 800 A
1 050 A
(L x 8.1) + 1.9 kg
1) Impedance can be up to 2.5 times higher if the cables are running close together but not twisted and up to 4 times higher if they are 1
meter apart.
Example, customised Multi-cable sets, length 2 x 5.0 m
Number
of cables
Cross section area Impedance
cables twisted
(mΩ)
Impedance ca-
bles not twisted
(mΩ)
Impedance ca-
bles 1 m apart
(mΩ)
Max. current in
20 sec.
Max. con-
tinuous
current
Weight
(total
set)
1 pair
120 mm
2
(1 x 120)
2.2
< 5.5
< 8.8
1 600 A
350 A
15.4 kg
2 pairs
240 mm
2
(2 x 120)
1.2
< 3.0
< 4.8
3 200 A
700 A
28.9 kg
3 pairs
360 mm
2
(3 x 120)
0.8
< 2.0
< 3.2
4 800 A
1 050 A
42.4 kg
Standard 2 X 5 m (single pair) cable set with clamps)
Cross section
area
Impedance
cables twisted
(mΩ)
Impedance ca-
bles not twisted
(mΩ)
Impedance ca-
bles 1 m apart
(mΩ)
Max. current
in 20 sec.
Max.
continuous
current
Weight
(total
set)
Article
number
120 mm
2
(1 x 120) 2.2
< 5.5
< 8.8
1 600 A
350 A
15.2 kg
GA-12052
Содержание INGVAR
Страница 2: ......
Страница 9: ...BH0654BE ZP BH05E 9 1 Safety...
Страница 17: ...BH0654BE ZP BH05E 17 2 Introduction...
Страница 19: ...BH0654BE ZP BH05E 19 4 Display...
Страница 33: ...BH0654BE ZP BH05E 33 5 Menu options...
Страница 47: ...BH0654BE ZP BH05E 47 5 Menu options...
Страница 67: ...BH0654BE ZP BH05E 67 Appendix 1...
Страница 70: ...70 ZP BH05E BH0654BE Index...
Страница 71: ......