8 APPLICATION EXAMPLES
tions ("OP" on the display) is increased by
one on the display. INGVAR stores the trip
(opening) times and reclosing times and the
currents that prevailed when each trip and
reclosing took place.
8]
Generation stops when you press the
OFF
button
or when the preset limited-time
generation period ("MAX TIME") is reached.
Display shows:
Total
time to
OFF
10.00s
RECL.
Actual
current
0A
3:OP
Number
of opera-
tions
9]
Press
to dump the test results via the
USB-port, see appendix 1.
10]
Press
ESC
to get more information on the
display:
Total
recl.
time
1)
9.015sTot
3:OP
First trip
pulse
985ms T1
39A
Current
at T1
1) Displayed provided generation continued until lock-out
11]
Turn the
Select/set knob
to get more infor-
mation displayed.
12]
Press
TIME
to start a new test.
13]
Press the
APPL
button to reset INGVAR to
normal use.
14]
Turn the
Select/set knob
until "NORMAL
USE" appears on the display.
15]
Press
and INGVAR will be reset for nor-
mal use.
8.5 Testing a sectionalizer
You can test a sectionalizer by making appropriate
changes in INGVAR’s settings. Here INGVAR sends out
a preset sequence of current pulses corresponding
to those that would be obtained from a direct-acting
automatic recloser. After the cycle is completed, the
following are stored and displayed:
The number of current pulses until lockout (number of
times the current is interrupted).
The total accumulated time (i.e. from the recloser’s
first trip until its last trip).
The trip times and the reclosing times.
The current at the first four trip occations.
Prior to the test 4 different puls-duration times (T1 -
T4) and the reclosing time (R1 - R4) can be set.
Note
After pulse T4 and R4 a pulse T5 and a pulse
R5 will be generated. T5 and R5 are identical
to T1 and R1. Use the "MAX TIME" function
to limit no. of pulses.
1]
Set the desired current, see section 7.3 "Set-
ting the desired current" for details.
2]
Press the
APPL
button.
3]
Turn the
Select/set knob
until "SECTIONAL-
IZER" appears in the display window.
4]
Press
.
5]
Set the time for T1 using the
Select/set knob
.
6]
Press
.
7]
Set the times for R1, T2, R2 etc.using the
Select/set knob
.
8]
Press
APPL
.
9]
If you want to use limited-time generation,
activate
MAX TIME
and set the desired maxi-
mum generation time.
10]
Press
TIME
or
MOM
to start the test.
11]
Generation stops when you press
OFF
button
, release the
MOM
button or when the
preset
MAX TIME
has been reached.
The display shows:
Total
time to
OFF
10.00s
SECT.
Actual
current
0A
2:OP
Pulses un-
til lockout
12]
Press
to dump the results via the USB-
port, see appendix 1.
Содержание INGVAR
Страница 2: ......
Страница 9: ...BH0654BE ZP BH05E 9 1 Safety...
Страница 17: ...BH0654BE ZP BH05E 17 2 Introduction...
Страница 19: ...BH0654BE ZP BH05E 19 4 Display...
Страница 33: ...BH0654BE ZP BH05E 33 5 Menu options...
Страница 47: ...BH0654BE ZP BH05E 47 5 Menu options...
Страница 67: ...BH0654BE ZP BH05E 67 Appendix 1...
Страница 70: ...70 ZP BH05E BH0654BE Index...
Страница 71: ......