8.1 Testing a low-voltage
circuit breaker
The following sections explain how to test a low-volt-
agecircuit breaker.
1]
Start by measuring the overcurrent stage’s
tripping limit and the tripping time.
2]
Then measure the tripping limit and tripping
time for the instantaneous unit.
Measuring the tripping limit
(normal generation)
Current is generated continuously and gradually in-
creased until the breaker trips. When the breaker trips
the current shown on the display is frozen and the
current is interrupted. When current first is generated
for a load (while the current is being set), INGVAR
adapts itself so that all subsequent generation opera-
tions start at the current’s zero-cross-over points. This
ensures minimized transient DC offset when the injec-
tion is initiated.
1]
Basic settings:
OPERATE
OFF
CURRENT ADJUST
Lower than the tripping
limit
HOLD function
ON
AUTO OFF
STOP INPUT
2]
Set the stop condition to
INT.
3]
Press
TIME
to start generation.
4]
Increase the current until tripping occurs (the
LATCH
lamp lights up).
5]
The current value frozen when tripping oc-
curred can now be read from the display.
Note
You can read out the highest current value
during an operation by pressing
ESC
repeat-
edly until "max" appears after a current value.
This value should be used for test objects
whose impedance changes during the opera-
tion.
Measuring the tripping time
1]
Set the current to an ample margin above
the tripping limit. The procedure is described
in section 7.3. Use the I/30 function (step 2 to
6 in section 7.3) if you want to set the cur-
rent without operating the breaker.
Note:
Disable the
INT
-function when you are
using I/30.
2]
Settings:
HOLD
ON
AUTO OFF
STOP INPUT
STOP INPUT
INT
3]
Press
TIME
or
MOM
to start generation
.
4]
Read the time and the current presented on
the display.
Instantaneous trip unit
measurement
When you test the instantaneous pick-up you can
provide a manually-controlled momentary current
injection by pressing the
MOM
button. This permits you
to find the instantaneous trip unit’s lowest operating
current without tripping the overcurrent stage.
1]
Basic settings:
OPERATE
OFF
CURRENT ADJUST
Close to the tripping
limit
HOLD function
ON
2]
Set the stop condition to
INT.
3]
Select a suitable current setting.
4]
Press
MOM
briefly. The time throughout which
current is generated must be shorter than
the overcurrent stage’s tripping time. You
can also use limited-time current generation
(
MAX TIME
). See section 7.13 "Measuring
operating limits".
5]
Change the current setting somewhat and
repeat from step 3 above until you find the
lowest current that provides tripping of the
instantaneous trip unit.
Содержание INGVAR
Страница 2: ......
Страница 9: ...BH0654BE ZP BH05E 9 1 Safety...
Страница 17: ...BH0654BE ZP BH05E 17 2 Introduction...
Страница 19: ...BH0654BE ZP BH05E 19 4 Display...
Страница 33: ...BH0654BE ZP BH05E 33 5 Menu options...
Страница 47: ...BH0654BE ZP BH05E 47 5 Menu options...
Страница 67: ...BH0654BE ZP BH05E 67 Appendix 1...
Страница 70: ...70 ZP BH05E BH0654BE Index...
Страница 71: ......