background image

www.megger.com

DLRO10 and DLRO10X

4

1. 

G

 SAFETY WARNINGS

 

„

These safety warnings must be read and understood before the instrument is used.

 

„

Whenever possible, circuits should be de-energised before testing. 

 

ƒ

If it is impossible to de-energise the circuit, (e.g. high voltage batteries cannot be switched off while their connections are tested) the user must 
be aware of the dangers. The instrument terminals will become live when connected to the circuit. Therefore when used on hazardous voltages 
custom Megger DH6, DH6-C test leads must be used.

 

„

Testing inductive circuits can be hazardous: 

 

ƒ

After testing an inductive load there will be an amount of energy stored in the inductance. This energy is released in the form of a discharge 
current. Disconnecting an inductive load while current is still flowing will cause a high voltage arc, which is a danger to both the user and the item 
under test. 

 

ƒ

Although the DLRO10 and DLRO10X are not designed as transformer ohmmeters the DLRO10 is fitted with a DISCHARGE lamp, marked ‘I’, which 
indicates that current is flowing in the C1-C2 loop. This lamp will flash at end of a test on an inductive load while a discharge current is still flowing 
and will stop flashing when the current has decayed to less than 1mA. DLRO10X uses a message on the display to achieve this. 

 

ƒ

For testing large inductive resistances the current carrying leads should be connected securely to the item under test before starting the test. It is 
not recommended that duplex handspikes be used to carry out tests on inductive loads. 

 

ƒ

If inadvertently using the DH4 handspikes on an inductive load, the L1 lamp on the handspikes will flash amber while discharge current flows, 
thereby duplicating the function of the ‘I’ lamp on the instrument. It is important to maintain contact until the L1 light stops flashing amber and 
turns green indicating the end of the test.

 

„

This product is not intrinsically safe. Do not use in an explosive atmosphere.

 

„

This instrument contains a lithium-ion high energy battery pack.

 

ƒ

Do not pierce, damage, disassemble or modify the battery. 

 

ƒ

The battery contains safety and protection devices, which if tampered with may cause the battery to generate heat, rupture or ignite.

 

ƒ

If a battery module is suspected to contain a faulty battery cells - do not ship the faulty battery module, either separately or inside an instrument.

 

ƒ

The instrument must be set to OFF and the lid must be installed and securely closed before the instrument is shipped.

 

ƒ

Do not heat or dispose of the battery in a fire.

 

ƒ

Do not subject the battery to strong impact, mechanical shock or excessive heat.

 

ƒ

Do not short-circuit or reverse the polarity of the battery pack.

Please note. The neck strap is specifically designed to break if subjected to a strain of approximately 50 kg.

Содержание DLRO-10

Страница 1: ...DLRO10 and DLRO 10X Digital Low Resistance Ohmmeter User Guide User Guide DLRO10 and DLRO10X Digital Low Resistance Ohmmeter...

Страница 2: ...ltage Warning 8 4 4 Discharge Current Warning 8 4 5 The Menu 8 4 6 Test Menu 9 4 7 Options Menu 9 4 7 1 Retrieve 9 4 7 2 Download 10 4 8 Passbands 10 4 9 Set Clock 11 4 10 Delete Data 11 4 11 Storage...

Страница 3: ...8 7 3 1 Standard Charging 18 7 3 2 WARNING 18 8 SPECIFICATIONS 19 9 TROUBLE SHOOTING 21 10 ACCESSORIES 22 11 REPAIR AND WARRANTY 24 11 1 Instrument Repair and Spare Parts 24 11 2 Approved Repair Compa...

Страница 4: ...to achieve this For testing large inductive resistances the current carrying leads should be connected securely to the item under test before starting the test It is not recommended that duplex handsp...

Страница 5: ...ectrical outlets CAT IV Measurement category IV Equipment connected between the origin of the low voltage mains supply and the distribution panel 1 1 Symbols used on the instrument G Caution Refer to...

Страница 6: ...at the back and held closed by magnetic catches covers the top panel This lid may be removed if required by opening fully and snapping out of its hinges Both instruments are protected against accident...

Страница 7: ...he lamp will not operate if the instrument is turned off The I lamp will light if a current greater than 1 mA is still flowing after a test is completed This suggests that an inductive load has been t...

Страница 8: ...measurement cannot be made if any of these messages is visible on the display 4 3 3 External Voltage Warning If external voltage is applied to the terminals a message EXT VOLTS will flash on the displ...

Страница 9: ...mode 4 7 Options Menu The Options menu has five options that are not related to each other as shown below There is a quick access menu that can be accessed using the numbers keys as follows 0 Retriev...

Страница 10: ...on allows you to set upper and lower limits between which the test result average must fall if it is to be signalled as a Pass GREEN Readings outside these limits will be signalled as a Fail RED Set t...

Страница 11: ...o clear DLRO10X s memory of stored data In case you have selected this Option by accident you will be asked to confirm that you wish to delete the data the default is NO Change this to YES and press E...

Страница 12: ...is automatically limited to 1A When Battery level is low 10 the maximum test current is automatically reduced by one level and will be further reduced when a test has to be abandoned because the batt...

Страница 13: ...he test number to 1 4 15 Keypad Operation The 12 key keypad is similar to those used on mobile telephones in that each key is capable of producing one of several characters depending on the number of...

Страница 14: ...ts on loads that exhibit an inductive component using the test mode indicated by the inductor symbol on the DLRO10 or by using the inductive mode on the DLRO10X When measuring inductive loads it is es...

Страница 15: ...as shown in the next section Testing Using Duplex Handspikes or Individual Leads One of the DH4 handspikes is fitted with two lamps marked L1 and L2 and an extra lead This lead should be plugged into...

Страница 16: ...two measurements Both measurements are displayed by DLRO 10X along with the average while the DLRO 10 displays the average only If the combined resistance of the current leads and test sample is grea...

Страница 17: ...e retaining clips and pull the top of the clip away from the instrument body The module now unplugs from the base of the instrument Plug in the charger or connect to a 12 volt vehicle type battery usi...

Страница 18: ...Charging The battery module is charging at its standard rate Fast Battery state flashing during charging indicates temperature fault 7 3 2 WARNING Connecting to greater than 15 volts can cause perman...

Страница 19: ...e and Safety LED Indication Measurement Mode Manual Auto Continuous Inductive Manual Auto Continuous Inductive Unidirectional Control Fully Automatic Fully Automatic with manual override of maximum cu...

Страница 20: ...to 122 F at reduced accuracy Storage 30 C to 70 C 22 F to 158 F Calibration 20 C 68 F Coefficient 0 01 per C from 5 C to 40 C 0 006 per F from 41 F to 104 F Standard charging 0 C to 40 C 32 F to 104...

Страница 21: ...RR 114 Checksum Failure in EEPROM Calibration constants have been lost The DLRO will continue to work but the accuracy can now not be guaranteed At switch on the display will show the software version...

Страница 22: ...3 172 DLRO10LPU UK Mains Line Power Unit UK plug 1003 093 DLRO10LPU US Mains Line Power Unit US plug 1003 171 DLRO10LPU line power unit The DLRO10 and DLRO10X may be also powered from an optional main...

Страница 23: ...06 18 9 m 30 ft 242006 30 Single Leads Single handspikes 2 for potential measurement 2 m 7 ft 242021 7 5 5 m 18 ft 242021 18 9 m 30 ft 242021 30 Current clips 2 for current connections 2 m 7 ft 242041...

Страница 24: ...r Repair If returning an instrument to the manufacturer for repair it should be sent freight pre paid to the appropriate address A copy of the Invoice and of the packing note should be sent simultaneo...

Страница 25: ...cell is located behind the display Dispose of in accordance with local regulations The lithium ion is classified as an industrial battery For disposal in the UK contact Megger Ltd For disposal of batt...

Страница 26: ...USA T 800 723 2861 USA only T 1 214 333 3201 F 1 214 331 7399 E USsales megger com Megger AB Rinkebyv gen 19 Box 724 SE 182 17 DANDERYD T 46 08 510 195 00 E seinfo megger com Megger USA Fort Collins...

Отзывы: