![Mean Well CMU2C Скачать руководство пользователя страница 36](http://html1.mh-extra.com/html/mean-well/cmu2c/cmu2c_installation-manual_1757957036.webp)
65
5
FC = 10
Request:
Response:
N* = Quantity of Registers
Starting Address
Starting Address
Byte Count
Byte Count
Registers Value
Registers Value
2 Bytes
2 Bytes
1 Byte
1 Byte
N* x 2 Bytes
N* x 2 Bytes
Quantity of Registers
Quantity of Registers
2 Bytes
2 Bytes
FC = 4
6
Request:
Response:
Starting Address
Byte Count
2 Bytes
1 Byte
Quantity of Input Registers
Input Register
2 Bytes
N* x 2 Bytes
System and PSU Settings (address range:0x0000~0x0038):
Turn all PSUs on/off.
ON: 0x0001
OFF: 0x0000
Turn PSU0 – PSU15
on/off.
ON: 0x0001
OFF: 0x0000
Turn PSU16 –
PSU31on/off.
ON: 0x0001
OFF: 0x0000
Turn PSU32 – PSU47
on/off.
ON: 0x0001
OFF: 0x0000
Register
Addresses
0x0000
0x0001
0x0002
0x0003
0x06、0x10
0x03、0x06、
0x10
0x03、0x06、
0x10
0x03、0x06、
0x10
2
2
2
2
Command
Name
OPERATION
(All)
OPERATION
(PSU#0~15)
OPERATION
(PSU#16~31)
OPERATION
(PSU#32~47)
Supported
Function Codes
# of data
Bytes
Description
66
5
0x0010
0x0011
0x0030
0x0031
0x0032
0x0033
0x0034
0x0035
0x0036
0x0037
0x0038
Command
Name
VOUT_SET
(All)
IOUT_SET
(All)
Relay1
Relay2
Relay3
Relay4
Digital
Output 1
(DOUT #1)
Digital
2
Output
2
(DOUT # )
Digital
3
Output
3
(DOUT # )
Digital
4
Output
4
(DOUT # )
Digital
5
Output
5
(DOUT # )
Set output voltage of
the all PSUs
(format: value, F=0.1)
Set output current of
the all PSUs
(format: value, F=0.1)
Relay1 setting
Relay setting
2
Relay setting
3
Relay setting
4
Digital output 1
setting
Digital output 2
setting
Digital output 3
setting
Digital output 4
setting
Digital output 5
setting
0x03、0x06、
0x10
0x03、0x06、
0x10
0x03、0x06、
0x10
0x03、0x06、
0x10
0x03、0x06、
0x10
0x03、0x06、
0x10
0x03、0x06、
0x10
0x03、0x06、
0x10
0x03、0x06、
0x10
0x03、0x06、
0x10
0x03、0x06、
0x10
2
2
2
2
2
2
2
2
2
2
2
# of data
Bytes
Description
Status Reading of CMU2 Relay and Digital IO (address range:0x0100~
0x0101):
Status reading of all
relays
Status reading of all
digital inputs and
outputs
0x0100
0x0101
0x03
0x03
2
2
Command
Name
Relay Status
Digital IO
Status
# of data
Bytes
Description
Register
Addresses
Register
Addresses
Supported
Function Codes
Supported
Function Codes