Each relay can flexibly set a source, a trigger definition and a

delay. After tapping a relay, triggering options will appear.

Please refer to the table below for detailed triggering functions.

The COMMON is connected to the NO (Normally Open) when

the trigger condition is met (shown as the right picture); The

COMMON is connected to the NC (Normally Closed) when the

trigger condition is NOT met (shown as the left picture).

Source

Alarm

(default)

PSU

On, Off

DI CH1 - DI CH5

High, Low

Trigger

Any (default),

OVP, OLP,Short,

OTP, AC-Fail,

Fan Lock

Delay

Immed.(default)、

1Sec、5Sec、10Sec、

30Sec、1~10Min

Source:

Alarm, PSU or digital input channels are available to be selected.

After selection, the corresponding trigger conditions will

appear. For instance: trigger definitions will move to relevant

protection options for the rack powers when alarm is selected.

Trigger definition:

(1)Alarm: trigger the output channel when one of the supplies

meets alarm conditions, such as OVP, OLP, short circuit or any

of the protections (default).

5

34

(2)PSU:

I. PSU ON: trigger the relay if one of the supplies is running
II. PSU OFF: trigger the relay if one of the supplies is remote

off or in alarm conditions.

III. PSU OFF: trigger the relay if all of the supplies are

disconnect.

(3)DI CH1 CH5(digital input channels): trigger the relay

according to condition of the selected input channel.

Delay:
Determine how long to delay before triggering the relay when
the trigger condition is met. There are imminently (default),

1Sec

10Min available

.

5.1.3.

ystem

5 S

5.1.3. . Network

5 1

System

provides settings for Network, Notice, ecurity, log

page

S

Config, Misc and Utility.

Password is required to enter the menu, the default password is

CMU2C

.

You can set the IP address on this

. The new settings will

page

take effect after power recycling.

Address

IP address

169 254 1.1

.

.

Subnet mask

255 255 0 0

.

. .

Default gateway

169 254 1.1

.

.

Default

5

Содержание CMU2C

Страница 1: ...CMU2C Pragramable Intelligent Smart UI Multi Industry General Purpose Smart Controller Installation manual F1 F3 F2 F4 HOT KEY Enter...

Страница 2: ...ts users can flexibly monitor specific events or alarms and take suitable action accordingly It not only being used to monitor the operating parameters and data of PSUs such as output voltage output c...

Страница 3: ...2 ED indication L 4 3 in signment of CN38 P as 4 4 in signment of CN39 P as 4 5 in signment of TB1 P as 4 6 in signment of TB30 P as 4 7 in signment of JK51 P as 4 8 in signment of JK52 P as 4 9 in s...

Страница 4: ...r eyes with running water for at least 15 minutes and consult a doctor 1 1 Password is required to edit network settings The following is the default password for the interfaces Touch panel interface...

Страница 5: ...Ohms 500VDC 25 70 RH Compliance to BS EN EN55032 CISPR32 Conduction Class B Radiation Class A BS EN EN61000 3 2 3 EAC TP TC 020 Compliance to BS EN EN61000 4 2 3 4 5 6 8 11 BS EN EN61000 6 1 BS EN EN5...

Страница 6: ...8 CN37 AOUT TB1 CN36 AIN CN39 DIN CN38 DOUT TB51 RS 485 2 1 JK53 RS 232 Slot 1 Slot 2 Slot 3 81 1 19 14 6 35 JK51 PMBus JK52 CANBus JK22 Ethernet 1 12 9 9 1 1 1 1 16 16 8 8 8 6 66 3 6 2 Accessory Stan...

Страница 7: ...ation Wiring 3 M4 25mm Plastic wall plug M4 20mm 230mm 52mm 3 1 1 Standalone Type 3 1 1 1 Wall Mounting 3 1 1 2 Accessory Installation Din Rail M3 6mm 8 3 Desktop M3 6mm M5 12mm 3 2 1 Rack mount type...

Страница 8: ...version Port JK52 Port JK600 and Port JK601 JK901 JK601 JK900 JK600 N If there are less than 16 devices connected to the communication ote port the vacant address will display disconnect For example...

Страница 9: ...pen the slot cover and insert the SD card Unlock the slot cover Close the slot cover 12 Rack mount type 3 5 1 1 Lock the slot cover Please use a Phillips screwdriver to remove the protective cover Unl...

Страница 10: ...t page Knob Used to quickly adjust values turning to increase the value clockwise and turning to decrease it This function is only valid in anti clockwise Output voltage current adjustment page Up and...

Страница 11: ...ignment of CN38 Pin No 1 3 5 7 9 2 4 6 8 10 Function DOUT 1 DOUT 2 DOUT 3 DOUT 4 DOUT 5 FG Description Common FG for DOUTx The isolated digital output signal with FG as reference Open collector signal...

Страница 12: ...ital input signal with FG as reference Open collector signal Open from F4 or 5V Logic 1 input to CMU2 Short to FG or 0V Logic 0 input to CMU2 The isolated digital input signal with FG as reference Ope...

Страница 13: ...l close contact of programmable relay1 Normal close contact of programmable relay2 Normal close contact of programmable relay3 Normal close contact of programmable relay4 Common for relay1 NO NC conta...

Страница 14: ...the CAN Bus interface Note Common FG for signal Note Isolated signal with FG as reference 4 Pin No Function Description 22 4 9 a Pin ssignment of JK22 JK22 1 8 8 1 TX TX RX FG FG RX FG FG 1 2 3 4 5 7...

Страница 15: ...ap the menu bar above to enter into other pages 5 Home options page The following functions are available in the home page 24 No 1 2 3 4 5 6 Name Menu bar Power information Real time operation curve S...

Страница 16: ...on added and displays as below 01 06 PSU address 0 7 02 06 PSU address 8 15 03 06 PSU address 16 23 04 06 PSU address 24 31 05 06 PSU address 31 39 06 06 PSU address 40 47 5 26 2 PSU operation status...

Страница 17: ...as it displays gray when the trigger condition is NOT met 5 28 The relay is used to display output state and setting page parameters of the four programmable relays Relay options page The following fu...

Страница 18: ...nctions to set output voltage page and current It also displays maximum and minimum adjustable values for user convenience Output adj options page The following functions are available in output adj p...

Страница 19: ...fault Low Delay Immed default 1Sec 5Sec 10Sec 30Sec 1 10Min 5 32 Trigger definitions 1 Alarm trigger the output channel when one of the supplies meets alarm conditions such as OVP OLP short circuit or...

Страница 20: ...Trigger definition 1 Alarm trigger the output channel when one of the supplies meets alarm conditions such as OVP OLP short circuit or any of the protections default 5 34 2 PSU I PSU ON trigger the r...

Страница 21: ...and new passwords and then tap Apply to change the password N ote 1 Up to 5 emails can be sent at a time the next email will be sent after one has been sent 2 The maximum content of a single mail is 3...

Страница 22: ...options 1Min 5Min 10Min 20Min 30Min 1Hr 2Hr and Never Default Never There are 10 options for brightness setting 10 100 Default 50 5 38 Log Config options page The following functions are available in...

Страница 23: ...Date Time language selection buzzer enabling and SD card formatting 5 No Name Description 40 Misc page options The following functions are available in Log Misc page 1 Date Time Tapping the boxes can...

Страница 24: ...n the CMU2 to recharge the capacitor at least once every three days 2 There are 25 options for time zone selection UTC 12 UTC 12 Default UTC 08 3 Up to 3 internet time servers available to be set usin...

Страница 25: ...ngle tap to display the next or previous pages Tap on the first page will jump to page 180 and vice versa 2 To jump to a certain page you can tap to use the keyboard 5 3 2 1 44 2 3 Data selection Data...

Страница 26: ...etting System requirements 1 Windows 10 2 AMD or Intel Pentium 133MHz or better based computer 3 10 100 BASE T Ethernet port 4 Google Chrome Firefox or Microsoft Edge Connection diagram IP setting You...

Страница 27: ...Only connect the PC to the CMU2 and make sure there is no other devices connected to the PC Click the Network and Internet Connections option Then click the Local Area Connection Select Internet Proto...

Страница 28: ...he route is Setting System Network Default IP 169 254 1 1 5 50 5 2 H 4 OME 5 2 S 5 TATUS 5 2 5 1 PSU Status The page of the built in web displays output power number HOME of PSU connected bus votage t...

Страница 29: ...rmal pen in green if the trigger condition N O is not met it will display NC ormal lose in gray N C 5 52 STATUS N normal open O N normal close C SOURCE Alarm PSU On Off DI CH1 5 High Low TRIGGER Any O...

Страница 30: ...are available to be selected After selection the corresponding trigger conditions will appear For instance trigger definitions will move to relevant protection options for the rack powers when alarm...

Страница 31: ...igger definition 1 Alarm rigger the output channel when one of the supplies T meets alarm conditions such as OVP OLP short circuit or any of the protections default 2 PSU I PSU ON rigger the relay if...

Страница 32: ...example If there is no data recorded then the month will be shown without red dot The data is readable in CSV format click the you want to view to month download it 5 8 58 5 2 8 SYSTEM 5 2 8 1 Networ...

Страница 33: ...ingle mail is 3000 bytes 3 Retransmission mechanism for transmission failure is 3 times with 10min time interval 4 Email sends when there is any new event log that occurs 60 5 2 8 3 Security 5 2 8 4 D...

Страница 34: ...nd then the Lo byte All Modbus TCP Message Frames are sent via TCP on registered port 502 For the IP Address please refer to Network page of the CMU2 5 3 2 Modbus Frame Encapsulation Modbus TCP messag...

Страница 35: ...tion protocol Number of following bytes including Unit Identifier Function code and Data Fields Identification of a remote slave connected on a serial line or on other buses Initialized by the client...

Страница 36: ...0031 0x0032 0x0033 0x0034 0x0035 0x0036 0x0037 0x0038 Command Name VOUT_SET All IOUT_SET All Relay1 Relay2 Relay3 Relay4 Digital Output 1 DOUT 1 Digital 2 Output 2 DOUT Digital 3 Output 3 DOUT Digital...

Страница 37: ...0x03 2 2 2 2 2 2 6 6 6 6 6 4 6 6 6 of data Bytes Description Status Reading of PSU PSU 0 47 address range 0x0200 0x0229 PSU number range 0 47 48 units in total N means Maximum register quantity for a...

Страница 38: ...2 8 Min 13 9 Min 14 10 Min Trigger Delay High byte Digital Output 1 5 0x0030 0x0033 Setting Low byte Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0 Trigger Delay Action Source 70 5 High byte Bit 0 3 Trigger...

Страница 39: ...orted circuit protected Bit 5 AC_FAIL AC abnormal flag 0 AC range abnormal 1 AC range abnormal Bit 6 OP_OFF DC status 0 DC turned on 1 DC turned off Bit 7 Internal high temperature alarm HI_TEMP 0 Int...

Страница 40: ...ange of 0x00 R00 0 0xFE R25 4 represents the firmware version of a MCU 0xFF represents on MCU existed EX The supply has two MCUs The firmware version of the MCU number1 is version R25 4 0xFE the MCU n...

Страница 41: ...04 0x04 0x0201 0x02 0x0001 0x157C 76 5 Request Request 5 3 6 Write Multiple Register FC 10 4 The request message specifies the multi register references to be written For example Client writes PSU 0 1...

Страница 42: ...f complete bytes of data Register Value The contents of event log The data needs to be converted into ASCII codes before reading 0x5053555F32312C46414E 204C6F636B2C323032322 F30312F31322031353A33 343A...

Страница 43: ...automatically after recycling the CMU2 4 6 7 Warranty This product provides five years warranty under normal usage Do not replace parts or any form of modification to the product in order to keep the...

Страница 44: ...No 28 Wuquan 3rd Rd Wugu Dist New Taipei City 248 Taiwan...

Отзывы: