55
Active:
Determine the logic level when outputting. High (high level):
5V; Low (low level): 0V.
Delay:
Determine how long to delay before outputting when the
trigger condition is met. There are imminently (default),
1Sec
… 10Min available
.
l
Relay
Relay is used to set four programmable relays to realize alarm
functions you need. In addition, the relays also can work with
digital inputs to do further applications
.
Each relay can flexibly set a source, a trigger definition and a
delay. After setting, click
to write your new parameters.
Please refer to the table below for detailed triggering functions.
APPLY
5
SOURCE
TRIGGER
Any (default),
OVP, OLP, Short,
OTP, AC-Fail,
Fan Lock
Alarm (default)
On, Off
PSU
High, Low
DI CH1 - DI CH5
DELAY
Immed.(default)、
1Sec、5Sec、10Sec、
30Sec、1~10Min
56
Source:
Alarm, PSU or digital input channels are available to be
selected. After selection, the corresponding trigger
conditions will appear. For instance: trigger definitions will
move to relevant protection options for the rack powers when
alarm is selected.
Trigger definition:
(1)Alarm: rigger the output channel when one of the supplies
T
meets alarm conditions, such as OVP, OLP, short circuit or
any of the protections (default).
(2)PSU: I. PSU ON: rigger the relay if one of the supplies is
T
running
II. PSU OFF: rigger the relay if one of the supplies is
T
remote off or in alarm conditions.
III. PSU OFF: rigger the relay if all of the supplies are
T
disconnect.
(3)DI CH1 CH5(digital input channels): rigger the relay
–
T
according to condition of the selected input channel.
Delay:
Determine how long to delay before triggering the relay when
the trigger condition is met. There are imminently (default),
1Sec
10Min available
…
.
5.2.7 LOG
5.2.7.1
ata og
D
L
LOG
provides data log and event log for users to view
page
operation status and diagnose problems that might arise.
N
: Please insert a SD card to enable data log and event log
ote
.
Data Log stores the measurement data at selected intervals
and provides a full history database for users to extract and
download. Date displays with a red dot if there is recorded
data. For example:
; If there is no data recorded, then the
date will be shown without red dot. The data is readable in
.CSV format, click the date you want to view to download it.
14