29
5.1.3.1 PSU on/off
5.1.3 Setting
The Setting page can do settings of PSU on/off, Output adj, I/O
signal, Rely and System.
Detailed information about the functions, please refer to following
section.
PSU on/off
provides users the ability to turn on/off the
page
PUSs, including all PSUs on/off and single PSU unit on/off.
PSU on/off
options
page –
The following functions are available in PSU on/off
:
page
No.
1
2
3
Name
Page
selection
Single
PSU
on/off
All PSU
on/off
Description
Users can tap
to select a desired page
to display. There are three pages in total as below:
01/03: PSU address 0 – 15
16 – 31
02/03: PSU address
–
03/03: PSU address 32 47
Tap specific PUS to control its on/off state.
Take PSU00 as an example:
To turn all PSUs on/off at the same time.
Note: If PSU is not online, you cannot control it
PSU00 ON
PSU00 OFF
5
1
3
2
30
5.1.3.2 Output adj
The output adj
provides functions to set output voltage
page
and current. It also displays maximum and minimum adjustable
values for user convenience
.
Output adj
options
page –
The following functions are available in output adj
:
page
No.
1
2
Name
Model
Voltage
adjustment
Description
Display model name of the rack power
1)
Use the slider bar to adjust the output
voltage. Tapping
buttons can fine adjust the
±
voltage in 0.1V unit. After choosing a desired
voltage value, tap
to write your new
voltage setting.
)
2
It will return to the current setting value if no
any action is taken.
Note: Voltage setting cannot exceed voltage
limitation of the rack power. Taking
DRP-3200-48 as an example is 24 – 60V
5
1
3
2
3
Current
adjustment
1) Use the slider bar to adjust the output
current. Tapping ± b uttons can fine adjust the
current in 0.1A unit. After choosing a desired
current value, tap to write your new
current setting.
2) It will return to the current setting value if no
any action is taken.
N
: Current setting cannot exceed current
ote
limitation of the rack power. Taking
DRP-3200-48 as an example is 13.5 73.5A
–