64
IMM AGS-2
OL
OL will alternately blink with the normal display on the LED display when
motor thermal overload content has reached 90% to 99% of its capacity.
OLL
The motor thermal overload content has reached 100%, and the motor has
stopped. The motor cannot be restarted until the overloaded motor has
cooled and OLt is displayed.
OLt
The motor thermal overload content has been reduced to 60% or less, and
the motor can be restarted.
ena
Passcode protection is enabled.
dis
Passcode is disabled.
oxx
xx = overload thermal content in percentage. Press the Down button to
toggle to this display.
cxx
xx = pending fault.
no
Attempted to change a passcode protected parameter without proper
security.
…
Three decimal places blink when remote display is active.
Fxx
xx Fault Code
Table 42, Fault Codes
Number
Description
Controlled
Stop
Auto
Reset
00
No Fault
--
--
01
UTS Time Limit Expired
Y
Y
02
Motor Thermal Overload Trip
Y
N
10
Phase Rotation Error, Not A-B-C
N
Y
12
Low Line Frequency
N
Y
13
High Line Frequency
N
Y
15
Input Power Not Three phase
N
Y
21
Low Line L1-L2 Voltage
Y
Y
22
Low Line L2-L3 Voltage
Y
Y
23
Low Line L3-L1 Voltage
Y
Y
24
High Line L1-L2 Voltage
Y
Y
25
High Line L2-L3 Voltage
Y
Y
26
High Line L3-L1 Voltage
Y
Y
27
Phase loss
N
Y
28
No Line Voltage
N
Y
30
I.O.C. (Instantaneous Overcurrent)
N
N
31
Overcurrent
Y
N
37
Current Imbalance
Y
Y
38
Ground Fault
Y
N
39
No Current At Run
N
Y
40
Shorted/Open SCR
N
N
47
Stack Protection Fault
N
Y
48
Bypass Contactor Fault (on STOP input)
Y
N
50
Control Power Low
N
Y
Continued next page