IMM AGS-2
69
Solid State Starter Settings
Operating Parameters Settings for Default Value and Settable Range:
Table 43, Starter Settings
No.
Operating Parameter
Default
Range of Setting
P1
Motor Full Load Amps (FLA)
1A
1 to 9999A
P2
Motor Rated Load Amps (RLA)
1A
1 to 9999A
P3
Motor Service Factor
1.25
1-1.99
P4
Motor Overload Class
10
1-40,Off
P5
Initial Motor Starting Current
225%
50 - 400%
P6
Max. Motor Starting Current
300%
100 – 800%
P7
Motor Ramp Time
7 sec
0 - 300 sec
P8
UTS time
10 sec
1 - 900 sec
P9
Stop Mode
Cos
Coast/Voltage decel
P10
Deceleration Level 1
40%
0 – 100%
P11
Deceleration Level 2
20%
0 – 50%
P12
Deceleration Time
2 sec
1 – 180 sec
P13
Default Meter Display
0(Status)
0-19
P14
Overcurrent Trip Level
140%
Off, 50 to 800%RLA
P15
Overcurrent Trip Time
2 sec
Off, .1 – 90 sec
P16
Rated RMS Voltage
460
100,110,120,200,208,220,230,24
0,350,380,400,415,440,460,480,
500,525,575,600,660,690,1000
P17
Overvoltage Trip Level
10%
Off, 1 – 40% rated volts
P18
Undervoltage Trip Level
10%
Off, 1 – 40% rated volts
P19
Over/Under Voltage Delay Time
1 Sec
.1-90 Sec
P20
Current Imbalance Trip Level
40%
5 - 40%
P21
Controlled Fault Stop
Off
Off, On
P22
Auto Fault Reset Delay Time
60
Off, 1 – 120 sec
P23
CT Ratio
2640
72,96,144,288,864,2640,2880,57
60,8000,14400,28800
P24
Control Source
Ter
Terminal/Network
P25
Modbus Address
2
1 - 247
P26
Modbus Baud Rate
19.2 Kbps
1.2,2.4,4.8,9.6,19.2 kbps
P27
Modbus Timeout
1 sec
Off, 1 – 120 sec
P28
Analog Output Function
1
1 - 11
P29
Analog Output Span
100%
1 – 125%
P30
Analog Output Offset
0%
0 – 99%
P31
Passcode
0-9999
P32
Fault Log
Display faults