9
Case 2, Two Units Side By Side
Two or more units sited side by side are common. If spaced closer than 12 feet (3.7 meters), or 8
feet (2.5 meters), depending on size, it is necessary to adjust the performance of each unit.
Circuits adjoining each other are affected.
NOTE:
This case applies only to
two
units side by side.
See Case 3 for three or more parallel units. If one of the two units also has a wall adjoining it, see
Case 1. Add the two adjustment factors together and apply to the unit located between the wall
and the other unit.
Mounting units end to end will not necessitate adjusting performance. Depending on the actual
arrangement, sufficient space must be left between the units for access to the control panel door
opening and/or evaporator tube removal. See “Clearance” section of this guide for requirements
for specific units.
Figure 6, Two Units Side by Side
Figure 7, Adjustment Factor
3.0
2.0
1.0
0
9
(2.7)
10
(3.0)
11
(3.3)
12
(3.6)
6.0
4.0
2.0
0
9
(2.7)
10
(3.0)
11
(3.3)
12
(3.6)